TROUBLE- SHOOTING
PROBLEM | PROBABLE CAUSE | CORRECTIVE ACTION |
| ||
Door will not open | 1. | Faulty door control | 1. | Insure input power is good at LO21P – orange and |
|
– all LED’s are | 2. | Faulty LO21P |
| brown wires. Should be 12 to 24 volts AC or DC. | |
OFF at the LO21P | 3. | Faulty | 2. | Go directly to door control and jumper common and | |
|
| Open switch |
| activation input. If door opens, proceed to next step. If | |
| 4. | Faulty Eagle |
| not, replace/repair faulty door control. | |
| 5. | Faulty wiring | 3. | Go to LO21P and jumper the red/white striped wire to | |
|
|
|
| the black/white striped wire. Green LED on LO21P | |
|
|
|
| should come on, and door should open. If not, replace | |
|
|
|
| LO21P. If LED comes on, but door does not open, check | |
|
|
|
| to insure that the blue and green wires are connected to | |
|
|
|
| the door control properly. | |
|
|
| 4. | Check to insure that | |
|
|
|
| functioning properly. | |
|
|
| 5. | Check Eagle sensor for proper operation. Jumper | |
|
|
|
| common and N.O. terminals while wires are attached. If | |
|
|
|
| door does not open, check wiring between Eagle and | |
|
|
|
| LO21P. | |
Door will not open | 1. Bodyguard is in detection | 1. | Launch a setup on Bodyguard |
| |
– red LED is ON at | 2. Bodyguard not | 2. | Insure Bodyguard relay output is programmed to a | ||
LO21P |
| programmed properly |
| value of 2. Default is 1. | |
| 3. Faulty wiring between | 3. | When Bodyguard is in detection, an open circuit | ||
|
| Bodyguard and LO21P |
| occurs at the purple and gray wires on the LO21P. | |
|
|
|
| Thus if there is any break in wiring between purple | |
|
|
|
| and gray and the LO21P, the lockout will react the | |
|
|
|
| same as if the Bodyguard were in detection. Insure | |
|
|
|
| there are no breaks in the wiring. | |
Door will not close | 1. | 1. | Place switch in On or Auto position |
| |
|
| is in Hold Open position | 2. | Launch a setup at Bodyguard | |
| 2. | Bodyguard is in detection | 3. | Remove wire from common and activate terminal at | |
| 3. | Faulty door control |
| door control, if door does not close, replace/repair | |
|
|
|
| faulty control. | |
Bodyguard keeps re- | 1. | Incorrect data polarity at | 1. | Insure that the white wire goes to terminal 6 of the |
|
learning with each door |
| Bodyguard |
| Bodyguard, and the red/white striped wire goes to | |
position | 2. | Insufficient voltage |
| terminal 7 of the Bodyguard | |
|
| switching at red and | 2. | When door is closed, there should be 0 volts | |
|
| black wire of LO21P |
| observed on the red and black wires of the LO21P. | |
|
|
|
| When the door is open, voltage should be greater | |
|
|
|
| than approximately 9 volts. If voltage is not great | |
|
|
|
| enough at red and black wires when door is open, | |
|
|
|
| the LO21P will not be able to send the correct data | |
|
|
|
| to the Bodyguard. Remember, polarity must also be | |
|
|
|
| correct. The red wire must ALWAYS connect to the | |
|
|
|
| positive wire of the motor, as observed during door | |
|
|
|
| open position. See important note on page 2. | |
As the door is closing, | 1. | Dipswitch 6 at LO21P is | 1. Place dipswitch 6 in opposite position and |
| |
the Bodyguard, upon |
| in wrong position |
| door | |
seeing the closing door, |
|
|
|
|
|
seems to reactivate the |
|
|
|
|
|
door to the open |
|
|
|
|
|
position |
|
|
|
|
|
IMPORTANT NOTE: When experiencing sensor system problems, it is recommended to disable the main power supply as to fully disable the system, until necessary repairs can be made.
COMPANY CONTACT
Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please call B.E.A., Inc. If you must wait for the following workday to call B.E.A., leave the door inoperable until satisfactory repairs can be made. Never sacrifice the safe operation of the automatic door or gate for an incomplete solution.