SET-UP INSTRUCTIONS

Upon completion of all wiring, proceed with the set-up as follows:

1.Insure that the On-Off-Hold Open switch is in the ON position, and insure that the door control is powered and operating normally.

2.Power the Bodyguard sensor and, using a BEA Remote Control, unlock the sensor and change the Output Configuration to a value of 2. If necessary, refer to the Bodyguard User’s Guide for programming instruction.

+

2

 

 

3.Power the LO-21P on with 12-24 VAC/VDC, and insure all sensors or other devices in the application are properly powered

4.Observe the green LED on the Bodyguard upon powering. With the door in the closed position, the green LED should begin blinking, then expire approximately 5 seconds thereafter to indicate a successful set-up for the closed-door position.

5.Activate the door to the open position, the Bodyguard should once again begin flashing green, then expire approximately 5 seconds thereafter to indicate a successful set-up for the open-door position. If the door goes into safety swing as soon as it starts to close and you have a time delay set for the length of the closing cycle, reverse the black and red wires to the motor input for DC units. Correct any faults before proceeding.

If the Bodyguard learns a “door closed” position, but does not execute a set-up for the “open door position”, place the door to a hold open position. With a BEA remote control, unlock the Bodyguard, and with the door in the open position, press the Magic Wand key

STOP and then the number 2 – the Bodyguard should begin flashing green to signify a set-up. If it does not, this will be a quick indication that the improper data is being sent for the “open door” position. Check to insure that data exists on the data lines leading into the Bodyguard. In the full open position, voltage should be approximately 9 to 12 volts DC. If it is not, check the data lines (White wire on terminal 6 and Red/White wire on terminal 7) for correct voltage (see chart).

CLOSED DOOR

OPEN DOOR

CLOSING DOOR

0 Volts DC

9 to 12 Volts DC

8 Volts DC

To perform a quick test by remote control to check motor wire polarity, perform the following:

Place On-Off-Hold switch in the ON or AUTO position.

Activate the door and immediately walk into the Bodyguard detection pattern while door is open. Door should be holding open at this point. Make sure there is no Eagle activation during this time.

Unlock the Bodyguard and press Magic Wand + 2. Green LED will begin flashing – If door closes while flashing green, check for correct polarity at the red and black wire from lockout.

6.Once the Bodyguard has learned the open and closed door positions, observe the green and red LED’s on the LO-21P. Walk in and out of the field of detection for the Bodyguard while the door is open, and then again when it is closed. The LED’s indicate the following:

‰GREEN LED: The green LED, when illuminated, indicates that there is detection at the Bodyguard while the door is in the open position.

If someone steps into the Bodyguard detection zone when the door is open, the LO-21P’s Green LED will illuminate to indicate that the Bodyguard will be connected to the activation circuitry of the door, thus holding the door open as long as there is detection.

Green LED will also illuminate when the activating device (Eagle) is triggered, or when On-Off- Hold Open switch is placed to the Hold Open position.

‰RED LED: The red LED, when illuminated, indicates that there is detection at the Bodyguard while the door is in the closed position. It may also indicate that there is an activation signal from the Eagle or the Hold Open switch.

When the door is closed, and someone steps into the detection zone of the Bodyguard, the red LED on the LO-21P will illuminate, indicating that it will ignore any activation signal it receives. Therefore, the door will remain closed until the Bodyguard detection zone is clear. Once the Bodyguard zone is clear and the door has been activated it will open and remain open for the hold time set by the motion sensor and/or door control, and will also hold open during detection at Bodyguard.

75.5079.08 20061129

Page 5 of 13

Page 5
Image 5
BEA LO-21P technical specifications SET-UP Instructions, Closed Door Open Door Closing Door