SETUP INSTRUCTION Cont.
7.Adjustment is necessary to configure the dipswitches to obtain the correct lock out time delay. To set the dipswitches( 1 through 5) for lock out time, perform the following:
Activate the door to the open position.
Time the overall door closing cycle
Configure the dip switches according to the chart on Page 4 for the lockout time that is required
Activate the door again to the open position
Stand outside of the Bodyguard detection pattern, and while the door is closing, observe the red LED on the Bodyguard
The red LED on the Bodyguard should NOT illuminate during the closing cycle. If it does, it is probably seeing the door at the very last degree or two of door closing, which would indicate that the lock out time needs to be slightly increased.
Reconfigure the dipswitches to add 1 second of lock out time.
When the lock out time is correct. The red LED will not illuminate during the entire closing cycle of the door.
8.The last test is to insure that the Bodyguard detects an object as soon as the door has stopped closing. Simply allow the doors to begin closing, and step in behind the doors, into the Bodyguards field of detection. The red LED shall illuminate and remain on at the Bodyguard, and at the
9.Set the dipswitches according to the chart below to achieve the desired lockout time. The total lockout time is the sum total of the dipswitches that are in the ON position. For easy reference, use the timetables below. Default time is 7 seconds (times are approximate).
Dipswitch # Time Delay (seconds)
11
22
34
48
516
DIPSWITCH 6, 7 and 8
OPERATION
Time | dip 1 | dip 2 | dip 3 | dip 4 | dip 5 |
Delay | 1 sec | 2 sec | 4 sec | 8 sec | 16 sec |
(sec) |
|
|
|
|
|
1 | on | off | off | off | off |
2 | off | on | off | off | off |
3 | on | on | off | off | off |
|
|
|
|
|
|
4 | off | off | on | off | off |
5 | on | off | on | off | off |
6 | off | on | on | off | off |
|
|
|
|
|
|
7 | on | on | on | off | off |
8 | off | off | off | on | off |
9 | on | off | off | on | off |
|
|
|
|
|
|
10 | off | on | off | on | off |
11 | on | on | off | on | off |
12 | off | off | on | on | off |
|
|
|
|
|
|
13 | on | off | on | on | off |
14 | off | on | on | on | off |
15 | on | on | on | on | off |
|
|
|
|
|
|
16 | off | off | off | off | on |
Time | dip 1 | dip 2 | dip 3 | dip 4 | dip 5 |
Delay | 1 sec | 2 sec | 4 sec | 8 sec | 16 sec |
(sec) |
|
|
|
|
|
17 | on | off | off | off | on |
18 | off | on | off | off | on |
19 | on | on | off | off | on |
|
|
|
|
|
|
20 | off | off | on | off | on |
21 | on | off | on | off | on |
22 | off | on | on | off | on |
|
|
|
|
|
|
23 | on | on | on | off | on |
24 | off | off | off | on | on |
25 | on | off | off | on | on |
|
|
|
|
|
|
26 | off | on | off | on | on |
27 | on | on | off | on | on |
28 | off | off | on | on | on |
|
|
|
|
|
|
29 | on | off | on | on | on |
30 | off | on | on | on | on |
31 | on | on | on | on | on |
|
|
|
|
|
|
Dipswitch 6 Position
ON (Default)
OFF
Dipswitch 7 and 8
Position
7 OFF / 8 ON (Default)
7 ON / 8 OFF
Description of Performance
The LO21P expects to see voltage coming in at the red and black wire while the door is in the Open position. Typical for DC motors.
The LO21P expects to see voltage coming in at the red and black wire while the door is in the Closed position.
Description of Performance
The LO21P CLOSES the Safety circuit (yellow wire) upon a Bodyguard Detection during the door closed position
The LO21P OPENS the Safety circuit (yellow wire) upon a Bodyguard Detection during the door closed position