Table 6. Vent Terminals for Outdoor Units.

SECTION 3.

Gas Supply and Piping

3.1Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The Copper Brute II gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.

Review the following instructions before proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Copper Brute II heaters are equipped to operate at elevations up to 10000 feet (3050m). Copper Brute II heaters may be adjusted to operate properly at altitudes above 2500 feet (see Section 6.4.2) and the input will be reduced if the heating value of the gas supply is below sea level values.

2.The maximum inlet gas pressure must not exceed 13" W.C (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).

3.Refer to Table 7, size supply.

4.Run gas supply line in accordance with all applicable codes.

5.Locate and install manual shutoff valves in accordance with state and local requirements.

6.A sediment trap must be provided upstream of the gas controls.

7.All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.

8.The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).

9.The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).

10.The appliance and its gas connection must be leak tested before placing it in operation.

11.Purge all air from gas lines.

 

 

Distance from Gas Meter

 

 

Model and

 

or Last Stage Regulator

 

 

 

0-31m

 

31-61m

 

61-91m

Gas Type

0-100'

100-200'

200-300'

500 natural

1-1/2"

3.8cm

2"

5.1cm

2"

5.1cm

500 propane

1"

2.5cm

1-1/2"

3.8cm

1-1/2"

3.8cm

750 natural

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

750 propane

1-1/2"

3.8cm

1-1/2"

3.8cm

2"

5.1cm

1000 natural

2"

5.1cm

2-1/2"

6.4cm

3"

7.6cm

1000 propane

1-1/2"

3.8cm

2"

5.1cm

2-1/2"

6.4cm

1250 natural

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

1250 propane

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

1500 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1500 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

1750 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1750 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

2000 natural

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2000 propane

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

Notes:

1.These figures are based on 1/2" (0.12kPa) water column pressure drop.

2.Check supply pressure and local code requirements before proceeding with work. 3.Pipe fittings must be considered when determining gas pipe sizing.

Table 7. Gas Piping Size.

Page 12
Image 12
Bradford-White Corp BWCV warranty SECTION Gas Supply and Piping, Internet Version for Reference Only, Bradford White