ERROR DISPLAYED

Internet Version for Reference Only

Copper Brute II

Page 35

 

 

 

 

ERROR DISPLAYED

VIEW

DESCRIPTION OF ERROR

The control was unable to read a piece of information from its EEPROM. The control will stop operation until all settings in the Adjust menu have been checked by the user or installer.

VIEW

BOIL OUT

VIEW

BOIL OUT

VIEW

BOIL IN

VIEW

BOIL IN

VIEW

BOILSUP

VIEW

BOILSUP

OUTDR VIEW

OUTDR VIEW

VIEW

TANK

VIEW

TANK

The control is no longer able to read the heater outlet sensor due to a short circuit. In this case, if the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor. Otherwise, the control will not operate the heater stages.

The control is no longer able to read the heater outlet sensor due to an open circuit. In this case, if the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor. Otherwise, the control will not operate the heater stages.

The control is no longer able to read the heater inlet sensor due to a short circuit. In this case, the control will continue operation.

The control is no longer able to read the heater inlet sensor due to an open circuit. In this case, the control will continue operation.

The control is no longer able to read the heater supply sensor due to a short circuit. In this case, if the heater outlet sensor is present and operational, the control will operate based on the heater outlet sensor. If the heater outlet sensor is not available and the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor.

Otherwise, the control will not operate the heater stages.

The control is no longer able to read the heater supply sensor due to an open circuit. In this case, if the heater outlet sensor is present and operational, the control will operate based on the heater outlet sensor. If the heater outlet sensor is not available and the heate inlet sensor is present and operational, the control will operate using the heater inlet sensor Otherwise, the control will not operate the heater stages.

The control is no longer able to read the outdoor sensor due to a short circuit. In this case, the control assumes an outdoor temperature of 32°F and continues operation.

The control is no longer able to read the outdoor sensor due to an open circuit. In this case, the control assumes an outdoor temperature of 32°F and continues operation.

The control is no longer able to read the tank sensor due to a short circuit. In this case the control will not operate the heater stages.

The control is no longer able to read the tank sensor due to an open circuit. In this case the control will not operate the heater stages.