Table 6 Ð 558D036 Air Delivery Ð Vertical Discharge Units (Alternate Motor)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ALTERNATE BELT DRIVE MOTOR |
|
|
|
|
|
|
|
|
| |||||||||
AIRFLOW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
| ||||||||
(Cfm) | 0.1 |
|
|
|
|
| 0.2 |
|
| 0.3 |
| 0.4 |
|
|
|
| 0.5 |
| 0.6 |
| 0.7 |
| 0.8 | ||||||||||
|
| Rpm |
| Watts |
| Rpm |
| Watts |
| Rpm |
| Watts | Rpm |
| Watts |
| Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | |||||
900 | 581 |
| 119 |
| 673 |
|
| 179 |
|
| 736 |
| 219 | 805 |
| 249 |
| 865 |
| 288 | 911 |
| 338 | 957 |
| 388 | 988 |
| 428 | ||||
1000 | 644 |
| 189 |
| 709 |
|
| 219 |
|
| 782 |
| 279 | 835 |
| 298 |
| 900 |
| 348 | 937 |
| 378 | 992 |
| 438 | 1039 |
| 487 | ||||
1100 | 687 |
| 219 |
| 746 |
|
| 259 |
|
| 806 |
| 298 | 867 |
| 348 |
| 929 |
| 398 | 964 |
| 398 | 1013 |
| 487 | 1068 |
| 547 | ||||
1200 | 733 |
| 259 |
| 785 |
|
| 318 |
|
| 843 |
| 348 | 903 |
| 408 |
| 960 |
| 467 | 994 |
| 497 | 1045 |
| 557 | 1090 |
| 637 | ||||
1300 | 754 |
| 288 |
| 826 |
|
| 378 |
|
| 891 |
| 428 | 942 |
| 477 |
| 991 |
| 527 | 1047 |
| 597 | 1075 |
| 637 | 1122 |
| 696 | ||||
1400 | 810 |
| 348 |
| 868 |
|
| 448 |
|
| 937 |
| 507 | 984 |
| 567 |
| 1032 |
| 617 | 1067 |
| 666 | 1110 |
| 726 | 1160 |
| 766 | ||||
1500 | 841 |
| 418 |
| 911 |
|
| 527 |
|
| 985 |
| 607 | 1029 |
| 656 |
| 1073 |
| 716 | 1109 |
| 766 | 1150 |
| 816 | 1190 |
| 855 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| ALTERNATE BELT DRIVE MOTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
AIRFLOW |
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
(Cfm) |
|
|
| 0.9 |
|
|
| 1.0 |
|
|
| 1.1 |
|
|
| 1.2 |
|
|
|
|
|
|
|
|
|
| |||||||
|
| Rpm |
| Watts |
|
| Rpm |
| Watts | Rpm |
| Watts |
| Rpm |
| Watts |
|
|
|
|
|
|
|
|
| ||||||||
900 |
| 1039 |
|
| 448 |
| 1061 |
|
| 487 |
| 1083 |
| 527 |
|
| 1105 | 567 |
|
|
|
|
|
|
|
|
| ||||||
1000 |
| 1061 |
|
| 507 |
| 1086 |
|
| 547 |
| 1111 |
| 587 |
|
| 1136 | 627 |
|
|
|
|
|
|
|
|
| ||||||
1100 |
| 1090 |
|
| 577 |
| 1109 |
|
| 607 |
| 1127 |
| 637 |
|
| 1145 | 666 |
|
|
|
|
|
|
|
|
| ||||||
1200 |
| 1109 |
|
| 647 |
| 1156 |
|
| 676 |
| 1203 |
| 706 |
|
| 1250 | 736 |
|
|
|
|
|
|
|
|
| ||||||
1300 |
| 1152 |
|
| 716 |
| 1190 |
|
| 756 |
| 1228 |
| 796 |
|
| 1266 | 836 |
|
|
|
|
|
|
|
|
| ||||||
1400 |
| 1181 |
|
| 806 |
| 1237 |
|
| 845 |
| 1293 |
| 885 |
|
| 1349 | 925 |
|
|
|
|
|
|
|
|
| ||||||
1500 |
| 1225 |
|
| 895 |
| 1271 |
|
| 945 |
| 1317 |
| 995 |
|
| 1363 | 1044 |
|
|
|
|
|
|
|
|
|
NOTES:
1.Boldface indicates a
2. indicates
3.indicates maximum usable watts of a
4.Maximum usable watts input is 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5.Values include losses for ®lters, unit casing, and wet coils.
6.Use of a
7.Alternate motor drive range: 760 to 1090 rpm. All other rpms require
8.To convert watts to bhp:
bhp =
watts input x motor efficiency
746
Motor efficiency = .75
Table 7 Ð 558D048 Air Delivery Ð Vertical Discharge Units (Standard Motor)
|
|
|
| STANDARD DIRECT DRIVE MOTOR |
|
| ||||
AIRFLOW |
|
| Low Speed |
|
|
| High Speed |
| ||
(Cfm) |
| 208 v | 230, 460, 575 v |
| 208 v | 230, 460, 575 v | ||||
| ESP |
| Watts | ESP | Watts | ESP |
| Watts | ESP | Watts |
1200 | 0.93 |
| 458 | 0.94 | 506 | 0.94 |
| 572 | 0.99 | 632 |
1300 | 0.86 |
| 471 | 0.87 | 521 | 0.87 |
| 589 | 0.92 | 651 |
1400 | 0.78 |
| 503 | 0.79 | 556 | 0.79 |
| 616 | 0.87 | 681 |
1500 | 0.70 |
| 536 | 0.73 | 593 | 0.73 |
| 631 | 0.80 | 698 |
1600 | 0.61 |
| 557 | 0.64 | 616 | 0.66 |
| 654 | 0.76 | 723 |
1700 | 0.51 |
| 584 | 0.54 | 646 | 0.58 |
| 678 | 0.68 | 750 |
1800 | 0.40 |
| 610 | 0.44 | 674 | 0.51 |
| 698 | 0.63 | 772 |
1900 | 0.29 |
| 629 | 0.37 | 696 | 0.46 |
| 720 | 0.56 | 796 |
2000 | 0.25 |
| 651 | 0.30 | 720 | 0.39 |
| 744 | 0.50 | 823 |
LEGEND
ESP Ð External Static Pressure (in. wg)
NOTES:
1.Values include losses for ®lters, unit casing, and wet coils.
2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
3.Use of a
4.To convert watts to bhp:
bhp =
watts input x motor efficiency
746
Motor efficiency = .66