TROUBLESHOOTING
Refer to Tables
Table 19 Ð Cooling Troubleshooting
PROBLEM | CAUSE | REMEDY | |
| Power failure. | Call power company. | |
| Fuse blown or circuit breaker tripped. | Replace fuse or reset circuit breaker. | |
Compressor and | Defective thermostat, contactor, transformer, or | Replace component. | |
control relay. | |||
condenser fan |
| ||
Insufficient line voltage. | Determine cause and correct. | ||
will not start. | |||
| Incorrect or faulty wiring. | Check wiring diagram and rewire correctly. | |
| Thermostat setting too high. | Lower thermostat setting below room | |
| temperature. | ||
|
| ||
| Faulty wiring or loose connections in compressor | Check wiring and repair or replace. | |
| circuit. | ||
|
| ||
Compressor will not start | Compressor motor burned out, seized, or internal | Determine cause. Replace compressor. | |
overload open. | |||
but condenser fan runs. |
| ||
Defective run/start capacitor, overload, start relay. | Determine cause and replace. | ||
| |||
| One leg of of | Replace fuse or reset circuit breaker. | |
| Determine cause. | ||
|
| ||
| Refrigerant overcharge or undercharge. | Recover refrigerant, evacuate system, and | |
| recharge to nameplate. | ||
|
| ||
| Defective compressor. | Replace and determine cause. | |
Compressor cycles | Insufficient line voltage. | Determine cause and correct. | |
Blocked condenser. | Determine cause and correct. | ||
(other than normally | |||
satisfying thermostat). | Defective run/start capacitor, overload, or start relay. | Determine cause and replace. | |
| Defective thermostat. | Replace thermostat. | |
| Faulty | Replace. | |
| Restriction in refrigerant system. | Locate restriction and remove. | |
| Dirty air ®lter. | Replace ®lter. | |
| Unit undersized for load. | Decrease load or increase unit size. | |
| Thermostat set too low. | Reset thermostat. | |
Compressor operates | Low refrigerant charge. | Locate leak; repair and recharge. | |
continuously. |
|
| |
Leaking valves in compressor. | Replace compressor. | ||
| |||
| Air in system. | Recover refrigerant, evacuate system, and | |
| recharge. | ||
|
| ||
| Condenser coil dirty or restricted. | Clean coil or remove restriction. | |
| Dirty air ®lter. | Replace ®lter. | |
| Dirty condenser coil. | Clean coil. | |
Excessive head pressure. | Refrigerant overcharged. | Recover excess refrigerant. | |
Air in system. | Recover refrigerant, evacuate system, and | ||
| |||
| recharge. | ||
|
| ||
| Condenser air restricted or air | Determine cause and correct. | |
| Low refrigerant charge. | Check for leaks; repair and recharge. | |
Head pressure too low. | Compressor valves leaking. | Replace compressor. | |
| Restriction in liquid tube. | Remove restriction. | |
Excessive suction | High heat load. | Check for source and eliminate. | |
Compressor valves leaking. | Replace compressor. | ||
pressure. | |||
Refrigerant overcharged. | Recover excess refrigerant. | ||
| |||
| Dirty air ®lter. | Replace ®lter. | |
| Low refrigerant charge. | Check for leaks; repair and recharge. | |
| Metering device or low side restricted. | Remove source of restriction. | |
Suction pressure too low. | Insufficient evaporator air¯ow. | Increase air quantity. Check ®lter and replace | |
| if necessary. | ||
|
| ||
| Temperature too low in conditioned area. | Reset thermostat. | |
| Outdoor ambient below 25 F. | Install | |
Evaporator fan |
|
| |
will not shut off. | Time off delay not ®nished. | Wait for | |
(Sizes |
|
| |
Compressor makes excessive | Compressor rotating in wring direction. | Reverse the | |
noise (558D072 scroll only). | described in | ||
|