Bryant 558D installation instructions Ð22Ð

Models: 558D

1 40
Download 40 pages 24.17 Kb
Page 22
Image 22
Ð22Ð

Table 8 Ð 558D048 Air Delivery Ð Vertical Discharge Units (Alternate Motor)

 

 

 

 

 

 

 

 

 

 

ALTERNATE BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

(Cfm)

 

0.1

0.2

 

 

0.3

 

 

0.4

0.6

 

 

0.7

 

0.8

 

1.0

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

1200

542

 

168

616

 

221

678

 

278

 

739

 

336

842

 

462

886

 

525

929

 

588

1008

 

704

1300

576

 

210

644

 

263

704

 

326

 

764

 

389

867

 

525

910

 

588

952

 

651

1029

 

788

1400

610

 

252

673

 

315

732

 

378

 

791

 

441

889

 

578

933

 

651

976

 

725

1052

 

826

1500

646

 

294

704

 

368

761

 

436

 

818

 

504

912

 

641

957

 

720

1001

 

777

1076

 

905

1600

681

 

347

735

 

420

790

 

494

 

845

 

567

920

 

695

931

 

772

1023

 

848

1100

 

995

1700

718

 

410

768

 

483

836

 

562

 

873

 

641

965

 

777

1005

 

853

1045

 

930

1124

 

1084

1800

754

 

473

801

 

557

851

 

641

 

900

 

725

992

 

858

1032

 

940

1071

 

1022

1147

 

1174

1900

791

 

546

836

 

630

832

 

720

 

828

 

809

1019

 

950

1058

 

1037

1097

 

1124

1169

 

1263

2000

828

 

630

870

 

714

864

 

809

 

858

 

904

1046

 

1053

1085

 

1139

1124

 

1237

1194

 

1373

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

1.1

1.2

 

 

1.4

 

 

1.6

1.8

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

 

Rpm

 

Watts

Rpm

 

Watts

 

 

 

 

 

 

 

 

 

1200

1052

 

762

1096

 

820

1134

 

835

 

1203

 

885

1242

 

969

 

 

 

 

 

 

 

 

 

1300

1065

 

846

1101

 

904

1174

 

1040

 

1229

 

1100

1277

 

1029

 

 

 

 

 

 

 

 

 

1400

1087

 

890

1121

 

918

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1183

 

1042

 

1255

 

1167

1305

 

1190

 

 

 

 

 

 

 

 

 

1500

1111

 

980

1145

 

1014

1208

 

1138

 

1274

 

1272

1337

 

1350

 

 

 

 

 

 

 

 

 

1600

1134

 

1069

1168

 

1100

1232

 

1253

 

1291

 

1396

1350

 

1558

 

 

 

 

 

 

 

 

 

1700

1158

 

1164

1192

 

1196

1255

 

1358

 

1314

 

1511

1370

 

1738

 

 

 

 

 

 

 

 

 

1800

1182

 

1263

1217

 

1301

1279

 

1473

 

1381

 

1635

1393

 

1907

 

 

 

 

 

 

 

 

 

1900

1205

 

1363

1240

 

1406

1303

 

1588

 

1408

 

1769

1417

 

2068

 

 

 

 

 

 

 

 

 

2000

1228

 

1472

1262

 

1511

1327

 

1702

 

1436

 

1894

1440

 

2229

 

 

 

 

 

 

 

 

 

NOTES:

1.Boldface indicates a ®eld-supplied drive is required. (See Note 7.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive are required.

3.indicates maximum usable watts of a factory-supplied motor.

4.Maximum usable watts input is 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.

5.Values include losses for ®lters, unit casing, and wet coils.

6.Use of a ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

7.Alternate motor drive range: 840 to 1185 rpm. All other rpms require ®eld-supplied drive.

8.To convert watts to bhp:

bhp =

watts input x motor efficiency

746

Motor efficiency = .75

Table 9 Ð 558D060 Air Delivery Ð Vertical Discharge Units (Standard Motor)

 

 

 

 

 

 

STANDARD DIRECT DRIVE MOTOR

 

 

 

 

AIRFLOW

 

 

Low Speed

 

 

 

Medium Speed

 

 

High Speed

 

(Cfm)

 

208 v

230, 460, 575 v

 

208 v

230, 460, 575 v

 

208 v

230, 460, 575 v

 

ESP

 

Watts

ESP

Watts

ESP

 

Watts

ESP

Watts

ESP

Watts

ESP

Watts

1500

0.88

 

750

1.20

791

1.19

 

782

1.36

845

1.38

875

1.44

949

1600

0.68

 

780

1.04

824

1.04

 

821

1.22

883

1.25

913

1.33

988

1700

0.51

 

810

0.89

857

0.89

 

861

1.09

921

1.13

950

1.22

1027

1800

0.35

 

839

0.73

891

0.74

 

900

0.96

959

1.00

988

1.11

1066

1900

0.26

 

873

0.58

924

0.59

 

940

0.86

997

0.88

1025

1.00

1105

2000

0.18

 

905

0.42

957

0.44

 

979

0.73

1035

0.78

1063

0.92

1144

2100

0.08

 

940

0.27

990

0.29

 

1018

0.59

1073

0.63

1101

0.81

1183

2200

Ð

 

Ð

0.19

1023

0.19

 

1035

0.46

1111

0.49

1138

0.69

1222

2300

Ð

 

Ð

0.11

1056

0.11

 

1076

0.34

1149

0.41

1176

0.59

1261

2400

Ð

 

Ð

0.03

1096

0.04

 

1113

0.19

1187

0.22

1213

0.43

1300

2500

Ð

 

Ð

Ð

Ð

Ð

 

Ð

0.09

1225

0.12

1251

0.34

1340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

ESP Ð External Static Pressure (in. wg)

NOTES:

1.Values include losses for ®lters, unit casing, and wet coils.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be af- fected. For additional information on motor performance, refer to Table 4.

3.Use of ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

4.To convert watts to bhp:

bhp =

watts input x motor efficiency

 

746

Motor efficiency = .67

Ð22Ð

Page 22
Image 22
Bryant 558D installation instructions Ð22Ð