Table 10 Ð 558D060 Air Delivery Ð Vertical Discharge Units (Alternate Motor)
|
|
|
|
|
|
|
|
|
|
|
| ALTERNATE BELT DRIVE MOTOR |
|
|
|
|
|
|
|
|
|
|
| |||||||
AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
|
|
| |||||||
(Cfm) |
| 0.1 |
| 0.2 |
| 0.4 |
| 0.6 |
| 0.8 |
| 1.0 |
| 1.2 |
| 1.4 |
| 1.6 |
| 1.8 | ||||||||||
| Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm | Watts | Rpm | Watts | Rpm | Watts | |||
1500 | 730 |
| 347 | 789 |
| 409 | 896 |
| 542 | 990 |
| 685 | 1072 |
| 848 | 1153 |
| 1022 | 1221 |
| 1196 | 1256 |
| 1328 | 1280 |
| 1349 | 1320 |
| 1400 |
1600 | 770 |
| 409 | 826 |
| 470 | 931 |
| 623 | 1020 |
| 766 | 1101 |
| 930 | 1178 |
| 1114 | 1252 |
| 1298 | 1311 |
| 1482 | 1340 |
| 1615 | 1380 |
| 1645 |
1700 | 811 |
| 480 | 865 |
| 552 | 966 |
| 705 | 1051 |
| 858 | 1133 |
| 1032 | 1205 |
| 1206 | 1278 |
| 1400 | 1345 |
| 1604 | 1397 |
| 1799 | 1424 |
| 1931 |
1800 | 852 |
| 562 | 905 |
| 634 | 1002 |
| 797 | 1084 |
| 950 | 1163 |
| 1124 | 1235 |
| 1318 | 1303 |
| 1512 | 1371 |
| 1727 | 1433 |
| 1942 | 1480 |
| 2136 |
1900 | 894 |
| 552 | 945 |
| 736 | 1037 |
| 899 | 1119 |
| 1063 | 1194 |
| 1237 | 1266 |
| 1431 | 1330 |
| 1625 | 1396 |
| 1850 | 1460 |
| 2074 | 1517 |
| 2299 |
2000 | 936 |
| 756 | 984 |
| 838 | 1072 |
| 1001 | 1154 |
| 1185 | 1226 |
| 1359 | 1297 |
| 1564 | 1362 |
| 1768 | 1422 |
| 1983 | 1485 |
| 2207 | 1544 |
| 2453 |
2100 | 978 |
| 869 | 1024 |
| 950 | 1108 |
| 1124 | 1192 |
| 1318 | 1259 |
| 1502 | 1327 |
| 1696 | 1393 |
| 1911 | 1452 |
| 2126 | 1510 |
| 2361 | 1569 |
| 2606 |
2200 | 1021 |
| 991 | 1064 |
| 1073 | 1145 |
| 1247 | 1225 |
| 1461 | 1294 |
| 1656 | 1359 |
| 1850 | 1423 |
| 2064 | 1483 |
| 2289 | 1538 |
| 2514 | 1595 |
| 2769 |
2300 | 1064 |
| 1124 | 1104 |
| 1206 | 1183 |
| 1390 | 1260 |
| 1604 | 1330 |
| 1819 | 1392 |
| 2013 | 1454 |
| 2228 | 1515 |
| 2463 | 1569 |
| 2698 | 1622 |
| 2943 |
2400 | 1107 |
| 1267 | 1145 |
| 1349 | 1222 |
| 1482 | 1296 |
| 1768 | 1365 |
| 1983 | 1426 |
| 2197 | 1485 |
| 2412 | 1544 |
| 2647 | 1601 |
| 2902 | 1652 |
| 3137 |
2500 | 1150 |
| 1420 | 1186 |
| 1512 | 1262 |
| 1717 | 1331 |
| 1931 | 1400 |
| 2166 | 1461 |
| 2391 | 1518 |
| 2606 | 1575 |
| 2841 | 1631 |
| 3096 | 1684 |
| 3352 |
NOTES:
1.Boldface indicates a
2. indicates
3.indicates maximum usable watts of a
4.Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5.Values include losses for ®lters, unit casing, and wet coils.
6.Use of a
7.Alternate motor drive range: 900 to 1300. All other rpms require
8.To convert watts to bhp:
bhp =
watts input x motor efficiency
746
Motor efficiency = .74
Table 11 Ð 558C072 Air Delivery Ð Vertical Discharge Units (Standard Motor)
|
|
|
|
|
|
|
|
|
| STANDARD BELT DRIVE MOTOR |
|
|
|
|
|
|
|
|
|
|
| ||||||
AIRFLOW |
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
|
|
| ||||||
(Cfm) |
| 0.1 |
| 0.2 |
| 0.4 |
| 0.6 |
| 0.8 |
| 1.0 | 1.2 | 1.4 | 1.6 | ||||||||||||
| Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm |
| Watts | Rpm | Watts | Rpm | Watts | Rpm | Watts | |||
1800 | 852 |
| 562 | 905 |
| 615 | 1002 |
| 739 | 1084 |
| 859 | 1163 |
| 998 | 1235 |
| 1156 | 1303 | 1318 | 1371 |
|
| 1499 | 1433 |
| 1638 |
1900 | 894 |
| 630 | 945 |
| 692 | 1037 |
| 818 | 1119 |
| 948 | 1194 |
| 1089 | 1266 |
| 1250 | 1330 | 1413 | 1396 |
|
| 1604 | 1460 |
| 1796 |
2000 | 936 |
| 708 | 984 |
| 771 | 1072 |
| 899 | 1154 |
| 1047 | 1226 |
| 1190 | 1297 |
| 1361 | 1362 | 1534 | 1422 |
|
| 1718 | 1485 |
| 1910 |
2100 | 978 |
| 795 | 1024 |
| 859 | 1108 |
| 998 | 1190 |
| 1156 | 1259 |
| 1310 | 1327 |
| 1473 | 1393 | 1656 | 1452 |
|
| 1840 | 1510 |
| 2041 |
2200 | 1021 |
| 891 | 1064 |
| 956 | 1145 |
| 1097 | 1225 |
| 1275 | 1294 |
| 1439 | 1359 |
| 1604 | 1423 | 1779 | 1483 |
|
| 1980 | 1538 |
| 2171 |
2300 | 1064 |
| 998 | 1104 |
| 1064 | 1183 |
| 1216 | 1260 |
| 1396 | 1330 |
| 1578 | 1392 |
| 1744 | 1454 | 1927 | 1515 |
|
| 2128 | 1569 |
| 2326 |
2400 | 1107 |
| 1114 | 1145 |
| 1182 | 1222 |
| 1353 | 1296 |
| 1534 | 1365 |
| 1718 | 1426 |
| 1901 | 1485 | 2084 | 1544 |
|
| 2283 | 1601 |
| 2459 |
2500 | 1150 |
| 1241 | 1186 |
| 1318 | 1262 |
| 1491 | 1331 |
| 1674 | 1400 |
| 1875 | 1461 |
| 2067 | 1518 | 2249 | 1575 |
|
| 2445 | Ð |
| Ð |
2600 | 1193 |
| 1387 | 1228 |
| 1465 | 1301 |
| 1648 | 1367 |
| 1831 | 1435 |
| 2041 | 1497 |
| 2240 | 1552 | 2428 | Ð |
|
| Ð | Ð |
| Ð |
2700 | 1237 |
| 1543 | 1269 |
| 1621 | 1341 |
| 1814 | 1404 |
| 1997 | 1471 |
| 2214 | 1532 |
| 2420 | Ð | Ð | Ð |
| Ð | Ð | Ð |
|
|
2800 | 1280 |
| 1718 | 1311 |
| 1796 | 1381 |
| 1989 | 1442 |
| 2180 | 1506 |
| 2394 | Ð |
| Ð | Ð | Ð | Ð |
| Ð | Ð | Ð |
|
|
2900 | 1324 |
| 1901 | 1354 |
| 1980 | 1420 |
| 2180 | 1481 |
| 2369 | 1542 |
| 2579 | Ð |
| Ð | Ð | Ð | Ð |
| Ð | Ð | Ð |
|
|
3000 | 1368 |
| 2093 | 1396 |
| 2171 | 1460 |
| 2369 | 1521 |
| 2571 | Ð |
| Ð | Ð |
| Ð | Ð | Ð | Ð |
| Ð | Ð | Ð |
|
|
NOTES:
1.Boldface indicates
2. indicates
3.indicates maximum usable watts of a
4.Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5.Values include losses for ®lters, unit casing and wet coils.
6.Use of a
7.Standard motor drive range: 1070 to 1460. All other rpms require
8.To convert watts to bhp:
bhp =
watts input x motor efficiency
746
Motor efficiency = .84