Bryant 558D installation instructions Ð25Ð

Models: 558D

1 40
Download 40 pages 24.17 Kb
Page 25
Image 25
Ð25Ð

Table 14 Ð 558D048 Air Delivery Ð Horizontal Discharge Units (Standard Motor)

 

 

 

 

STANDARD DIRECT DRIVE MOTOR

 

 

AIRFLOW

 

 

Low Speed

 

 

 

High Speed

 

(Cfm)

 

208 v

230, 460, 575 v

 

208 v

230, 460, 575 v

 

ESP

 

Watts

ESP

Watts

ESP

 

Watts

ESP

Watts

1200

0.93

 

458

0.97

506

1.04

 

572

1.09

632

1300

0.86

 

471

0.90

521

0.96

 

589

1.02

651

1400

0.78

 

503

0.84

556

0.90

 

616

0.96

681

1500

0.73

 

536

0.76

593

0.83

 

631

0.89

698

1600

0.67

 

557

0.70

616

0.75

 

654

0.82

723

1700

0.60

 

584

0.63

646

0.67

 

678

0.74

750

1800

0.51

 

610

0.54

674

0.62

 

698

0.69

772

1900

0.40

 

629

0.45

696

0.54

 

720

0.62

796

2000

0.32

 

661

0.33

731

0.47

 

744

0.54

823

 

 

 

 

 

 

 

 

 

 

 

LEGEND

ESP Ð External Static Pressure (in. wg)

NOTES:

1.Values include losses for ®lters, unit casing, and wet coils.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.

3.Use of a ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

4.To convert watts to bhp:

bhp =

watts input x motor efficiency

 

746

Motor efficiency = .66

Table 15 Ð 558D048 Air Delivery Ð Horizontal Discharge Units (Alternate Motor)

 

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

0.1

0.2

 

0.3

 

 

0.4

 

 

0.6

 

 

 

 

 

0.7

0.8

 

 

1.0

 

Rpm

 

Watts

Rpm

 

Watts

 

Rpm

 

Watts

 

Rpm

 

Watts

 

Rpm

 

Watts

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

1200

514

 

158

590

210

 

657

263

 

723

 

315

 

828

 

441

 

876

 

510

924

 

578

999

 

674

1300

545

 

189

615

242

 

680

305

 

744

 

368

 

849

 

494

 

895

 

562

940

 

630

1025

 

756

1400

577

 

221

642

284

 

704

347

 

766

 

410

 

870

 

546

 

915

 

620

959

 

693

1042

 

828

1500

609

 

273

670

326

 

729

394

 

788

 

462

 

892

 

609

 

936

 

683

980

 

757

1060

 

899

1600

642

 

315

699

378

 

755

447

 

811

 

515

 

913

 

672

 

957

 

751

1001

 

830

1080

 

971

1700

675

 

378

728

441

 

782

510

 

836

 

578

 

935

 

746

 

979

 

825

1023

 

904

1101

 

1053

1800

709

 

431

759

504

 

810

578

 

860

 

651

 

957

 

820

 

1001

 

904

1044

 

988

1122

 

1134

1900

743

 

504

790

578

 

838

651

 

886

 

725

 

980

 

904

 

1023

 

993

1066

 

1082

1143

 

1237

2000

778

 

578

836

651

 

875

730

 

913

 

809

 

1004

 

988

 

1046

 

1082

1088

 

1177

1165

 

1339

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

1.1

 

1.2

 

 

1.4

 

 

 

 

1.6

 

 

 

 

1.8

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

 

Rpm

 

Watts

 

Rpm

 

Watts

 

 

 

 

 

 

 

 

 

 

1200

1018

 

685

1036

 

695

 

1073

 

756

 

 

1109

 

794

 

1138

 

851

 

 

 

 

 

 

 

 

 

 

1300

1058

 

807

1090

 

858

 

1121

 

832

 

 

1159

 

918

 

1193

 

976

 

 

 

 

 

 

 

 

 

 

1400

1080

 

899

1118

 

971

 

1175

 

1014

 

 

1206

 

1042

 

1244

 

1138

 

 

 

 

 

 

 

 

 

 

1500

1098

 

981

1136

 

1063

 

1205

 

1138

 

 

1258

 

1243

 

1289

 

1282

 

 

 

 

 

 

 

 

 

 

1600

1117

 

1058

1153

 

1140

 

1224

 

1234

 

 

1287

 

1387

 

1337

 

1492

 

 

 

 

 

 

 

 

 

 

1700

1137

 

1139

1172

 

1226

 

1241

 

1320

 

 

1307

 

1492

 

1366

 

1655

 

 

 

 

 

 

 

 

 

 

1800

1157

 

1226

1192

 

1318

 

1258

 

1415

 

 

1323

 

1597

 

1385

 

1779

 

 

 

 

 

 

 

 

 

 

1900

1179

 

1328

1214

 

1420

 

1279

 

1511

 

 

1341

 

1702

 

1402

 

1894

 

 

 

 

 

 

 

 

 

 

2000

1200

 

1431

1235

 

1523

 

1300

 

1616

 

 

1361

 

1817

 

1419

 

2008

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Boldface indicates a ®eld-supplied drive is required. (See Note 7.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive are required.

3.indicates maximum usable watts of a factory-supplied motor.

4.Maximum usable watts input is 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.

5.Values include losses for ®lters, unit casing, and wet coils.

6.Use of a ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

7.Alternate motor drive range: 840 to 1185 rpm. All other rpms require ®eld-supplied drive.

8.To convert watts to bhp:

bhp =

watts input x motor efficiency

746

Motor efficiency = .75

Ð25Ð

Page 25
Image 25
Bryant 558D installation instructions Ð25Ð