Bryant 558D installation instructions Ð26Ð

Models: 558D

1 40
Download 40 pages 24.17 Kb
Page 26
Image 26
Ð26Ð

Table 16 Ð 558D060 Air Delivery Ð Horizontal Discharge Units (Standard Motor)

 

 

 

 

 

 

STANDARD DIRECT DRIVE MOTOR

 

 

 

 

AIRFLOW

 

 

Low Speed

 

 

 

Medium Speed

 

 

High Speed

 

(Cfm)

 

208 v

230, 460, 575 v

 

208 v

230, 460, 575 v

 

208 v

230, 460, 575 v

 

ESP

 

Watts

ESP

Watts

ESP

 

Watts

ESP

Watts

ESP

Watts

ESP

Watts

1500

1.01

 

750

1.25

791

1.26

 

782

1.46

845

1.46

875

1.52

949

1600

0.82

 

780

1.09

824

1.11

 

821

1.32

883

1.33

913

1.41

988

1700

0.64

 

810

0.97

857

0.99

 

861

1.22

921

1.24

950

1.33

1027

1800

0.44

 

839

0.81

891

0.84

 

900

1.09

959

1.11

988

1.22

1066

1900

0.32

 

869

0.66

924

0.69

 

940

0.96

997

0.99

1025

1.11

1105

2000

0.21

 

899

0.47

957

0.51

 

979

0.80

1035

0.83

1063

0.97

1144

2100

0.13

 

929

0.32

990

0.36

 

1018

0.64

1073

0.71

1101

0.86

1183

2200

0.05

 

959

0.19

1023

0.21

 

1058

0.50

1111

0.58

1138

0.75

1222

2300

Ð

 

Ð

0.08

1057

0.08

 

1097

0.34

1149

0.39

1176

0.57

1261

2400

Ð

 

Ð

Ð

Ð

Ð

 

Ð

0.24

1187

0.29

1213

0.49

1300

2500

Ð

 

Ð

Ð

Ð

Ð

 

Ð

0.15

1225

0.15

1251

0.34

1340

LEGEND

ESP Ð External Static Pressure (in. wg)

NOTES:

1.Values include losses for ®lters, unit casing, and wet coils.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be af- fected. For additional information on motor performance, refer to Table 4.

3.Use of ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

4.To convert watts to bhp:

bhp =

watts input x motor efficiency

 

746

Motor efficiency = .67

Table 17 Ð 558D060 Air Delivery Ð Horizontal Discharge Units (Alternate Motor)

 

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE BELT DRIVE MOTOR

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

 

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

1500

658

 

276

722

 

337

840

 

470

937

 

603

1027

 

756

1108

 

920

1186

 

1104

1263

 

1328

1343

 

1615

1431

 

1829

1600

693

 

327

754

 

388

867

 

531

963

 

664

1052

 

828

1130

 

991

1205

 

1175

1278

 

1380

1350

 

1645

1424

 

1921

1700

729

 

388

787

 

450

895

 

593

991

 

746

1075

 

899

1154

 

1083

1226

 

1257

1296

 

1451

1364

 

1676

1432

 

1931

1800

765

 

460

821

 

521

923

 

664

1019

 

828

1099

 

981

1178

 

1165

1249

 

1349

1316

 

1553

1382

 

1758

1447

 

1993

1900

802

 

531

854

 

593

953

 

746

1046

 

920

1126

 

1083

1201

 

1257

1274

 

1461

1338

 

1656

1402

 

1870

1464

 

2095

2000

840

 

613

900

 

674

984

 

838

1073

 

1012

1154

 

1185

1226

 

1359

1297

 

1564

1363

 

1768

1424

 

1983

1484

 

2207

2100

878

 

705

923

 

766

1015

 

930

1101

 

1104

1182

 

1298

1252

 

1482

1320

 

1676

1388

 

1891

1448

 

2115

1505

 

2340

2200

916

 

797

958

 

869

1046

 

1032

1129

 

1216

1209

 

1420

1280

 

1615

1345

 

1809

1410

 

2013

1473

 

2248

1529

 

2483

2300

954

 

910

993

 

981

1079

 

1155

1160

 

1339

1237

 

1543

1309

 

1747

1372

 

1952

1434

 

2156

1496

 

2391

1554

 

2637

2400

993

 

1022

1029

 

1093

1112

 

1277

1190

 

1461

1264

 

1666

1336

 

1891

1400

 

2105

1459

 

2310

1519

 

2534

1578

 

2820

2500

1031

 

1155

1066

 

1226

1145

 

1420

1220

 

1640

1292

 

1809

1363

 

2044

1428

 

2269

1486

 

2483

1543

 

2708

1600

 

2953

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Boldface indicates a ®eld-supplied drive is required. (See Note 7.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive are required.

3.indicates maximum usable watts of a factory-supplied motor.

4.Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.

5.Values include losses for ®lters, unit casing, and wet coils.

6.Use of a ®eld-supplied motor may affect wire sizing. Contact your distributor to verify.

7.Alternate motor drive range: 900 to 1300. All other rpms require ®eld-supplied drive.

8.To convert watts to bhp:

bhp =

watts input x motor efficiency

746

Motor efficiency = .74

Ð26Ð

Page 26
Image 26
Bryant 558D installation instructions Ð26Ð