580J

Table 32 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)

Economizer

 

 

 

 

3 --- 6 TONS

 

 

 

 

 

 

 

 

 

 

 

CFM (in. wg)

600

800

1000

1250

1500

 

1750

2000

2250

2500

2750

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical

0.01

0.02

0.04

0.05

0.07

 

0.09

0.12

0.15

0.18

0.22

0.26

 

 

 

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.02

0.03

0.04

0.06

0.08

 

0.10

0.13

0.15

0.18

0.23

0.28

 

 

 

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 --- 12.5 TONS

 

 

 

 

 

 

 

 

CFM (in. wg)

2250

2500

2750

3000

3250

 

3500

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical

0.06

0.08

0.09

0.12

0.13

 

0.15

0.17

0.20

0.22

0.25

0.29

0.33

0.36

0.40

0.44

0.48

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

0.08

0.10

0.13

0.15

0.18

 

0.21

0.25

0.28

0.30

0.34

0.39

0.43

0.47

0.51

0.56

0.60

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Perfect Humidity

 

 

 

 

 

3---6 TONS

 

 

 

 

CFM (in. wg)

1000

1250

1500

1750

2000

2250

2500

2750

3000

3

Tons

0.04

0.052

0.07

---

---

---

---

---

---

4 Tons

---

0.106

0.138

0.172

0.21

---

---

---

---

5 Tons

---

---

0.138

0.172

0.21

0.252

0.30

---

---

6 Tons

---

---

---

0.112

0.125

0.161

0.19

0.22

0.25

 

 

 

 

 

 

 

7.5---12.5 TONS

 

 

 

 

 

 

 

 

CFM (in. wg)

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

7.5 Tons

0.12

0.14

0.16

0.19

0.21

0.23

0.26

---

---

---

---

---

---

---

---

---

8.5 Tons

---

0.11

0.12

0.13

0.15

0.17

0.18

0.20

0.22

---

---

---

---

---

---

---

10 Tons

---

---

---

0.13

0.15

0.17

0.18

0.20

0.22

0.24

0.26

0.28

---

---

---

---

12.5 Tons

---

---

---

---

---

0.17

0.18

0.20

0.22

0.24

0.26

0.28

0.31

0.33

0.36

0.39

General fan performance notes:

1.Interpolation is permissible. Do not extrapolate.

2.External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.

3.Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses, as shown in the tables above. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.

4.The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work, Bryant recommended the lower horsepower option.

5.For information on the electrical properties of Bryant motors, please see the Electrical information section of this book.

6.For more information on the performance limits of Bryant motors, see the application data section of this book.

7.The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy efficient motor. Variable speed motors are exempt from EPACT compliance require- ments. Therefore, the indoor fan motors for Bryant 580J04-14 units are exempt from these requirements.

48

Page 48
Image 48
Bryant 580J manual Static Pressure Adders Factory Options and/or Accessories, Tons