Bryant 580J manual FAN PERFORMANCE cont, Pulley Adjustment, Factory settings

Models: 580J

1 86
Download 86 pages 11.72 Kb
Page 60
Image 60
Table 55 – PULLEY ADJUSTMENT

580J

FAN PERFORMANCE (cont.)

Table 55 – PULLEY ADJUSTMENT

UNIT

MOTOR/DRIVE

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

COMBO

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

 

 

 

phase1

Standard Static

854

825

795

766

736

707

678

648

619

589

560

 

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

 

04

 

High Static

---

---

---

---

---

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

phase3

Standard Static

854

825

795

766

736

707

678

648

619

589

560

 

 

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

 

 

 

High Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase1

Standard Static

854

825

795

766

736

707

678

648

619

589

560

 

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

 

05

 

High Static

---

---

---

---

---

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

phase3

Standard Static

854

825

795

766

736

707

678

648

619

589

560

 

 

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

 

 

 

High Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase1

Standard Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

Medium Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

 

 

06

 

High Static

---

---

---

---

---

---

---

---

---

---

---

 

 

 

 

 

 

 

 

 

 

 

 

 

phase3

Standard Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

 

 

Medium Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

 

 

 

 

High Static

1687

1649

1610

1572

1533

1495

1457

1418

1380

1341

1303

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

1457

1419

1380

1342

1303

1265

1227

1188

1150

1111

1073

07

Medium Static

1518

1484

1449

1415

1380

1346

1311

1277

1242

1208

1173

 

 

 

3

High Static

1788

1757

1725

1694

1662

1631

1600

1568

1537

1505

1474

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

747

721

695

670

644

618

592

566

541

515

489

08

Medium Static

949

927

906

884

863

841

819

798

776

755

733

 

 

 

3

High Static

1102

1083

1063

1044

1025

1006

986

967

948

928

909

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

733

712

690

669

647

626

604

583

561

540

518

09

Medium Static

936

911

887

862

838

813

788

764

739

715

690

 

 

 

3

High Static

1084

1059

1035

1010

986

961

936

912

887

863

838

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

838

813

789

764

739

715

690

665

640

616

591

12

Medium Static

1084

1059

1035

1010

986

961

936

912

887

863

838

 

 

 

3

High Static

1240

1218

1196

1175

1153

1131

1109

1087

1066

1044

1022

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

838

813

789

764

739

715

690

665

640

616

591

14

Medium Static

1084

1059

1035

1010

986

961

936

912

887

863

838

 

 

 

3

High Static

1240

1218

1196

1175

1153

1131

1109

1087

1066

1044

1022

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Do not adjust pulley further than 5 turns open.

 --- Factory settings --- Factory settings

60

Page 60