FAN PERFORMANCE

Table 33 – 580J*04

 

 

 

1 PHASE

 

 

3 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

CFM

 

0.2

 

0.4

0.6

 

 

0.8

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Field Supplied Drive1

 

Standard Static Option

 

 

Medium Static Option

900

 

553

0.14

681

0.22

782

0.32

870

0.42

948

0.53

975

 

575

0.16

700

0.25

801

0.35

888

0.46

965

0.57

1050

 

597

0.18

720

0.28

820

0.38

906

0.49

983

0.61

1125

 

620

0.21

741

0.31

839

0.42

925

0.54

1001

0.66

1200

 

643

0.23

762

0.34

 

 

944

0.58

1020

0.71

859

0.46

1275

 

667

0.27

783

0.38

879

0.50

963

0.63

1038

0.76

1350

 

691

0.30

805

0.42

900

0.55

983

0.68

1057

0.82

1425

 

715

0.34

827

0.47

920

0.60

1002

0.74

1076

0.88

1500

 

740

0.38

849

0.52

941

0.66

1023

0.80

1096

0.95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

CFM

 

 

1.2

 

1.4

1.6

 

 

1.8

 

2.0

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

Medium Static Option

 

 

 

Field Supplied Drive2

 

900

 

1019

0.64

1084

0.76

1146

0.89

1203

1.02

1258

1.16

975

 

1036

0.69

1101

0.81

1162

0.94

1219

1.08

---

---

1050

 

1053

0.74

1118

0.86

 

 

1236

1.14

---

---

 

1179

1.00

1125

 

1071

0.79

1135

0.92

1196

1.06

1253

1.20

---

---

1200

 

1089

0.84

1153

0.98

1213

1.12

---

---

---

---

1275

 

1107

0.90

1171

1.04

1231

1.19

---

---

---

---

1350

 

1126

0.96

 

 

---

---

---

---

---

---

 

1189

1.11

1425

 

1144

1.03

1208

1.18

---

---

---

---

---

---

1500

 

1163

1.10

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field supplied drive is required.

1.Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).

2.Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).

Table 34 – 580J*04

 

 

 

1 PHASE

 

 

3 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

1.0

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

Field Supplied Drive1

 

Standard Static Option

 

Medium Static Option

 

900

567

0.15

688

0.22

786

 

0.30

871

0.37

947

0.44

975

591

0.17

710

0.26

807

 

0.34

891

0.42

966

0.49

1050

615

0.20

732

0.29

828

 

0.38

911

0.47

985

0.55

1125

641

0.23

755

0.33

849

 

0.42

931

0.52

1005

0.61

1200

666

0.26

778

0.37

 

 

0.47

952

0.57

1025

0.67

871

1275

693

0.29

802

0.41

893

 

0.53

974

0.63

1046

0.74

1350

719

0.33

826

0.46

916

 

0.58

995

0.70

1067

0.81

1425

746

0.38

850

0.51

939

 

0.64

1017

0.76

1088

0.89

1500

773

0.42

 

 

963

 

0.70

1040

0.84

1110

0.96

875

0.57

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

2.0

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

 

Field Supplied Drive2

 

900

1016

0.51

1080

0.57

1139

 

0.64

1195

0.71

1249

0.77

975

1034

0.57

1098

0.64

1157

 

0.72

1213

0.79

1266

0.86

1050

1053

0.63

1116

0.71

 

 

0.79

1231

0.87

1284

0.95

1176

 

1125

1073

0.70

1135

0.79

1194

 

0.87

1250

0.96

1302

1.04

1200

1093

0.77

1155

0.87

1213

 

0.96

1268

1.05

1321

1.14

1275

1113

0.85

1174

0.95

1232

 

1.05

1287

1.15

---

---

1350

1133

0.92

 

 

1252

 

1.14

---

---

---

---

1194

1.03

 

1425

1154

1.01

1215

1.12

---

 

---

---

---

---

---

1500

1175

1.09

---

---

---

 

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field supplied drive is required.

1.Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).

2.Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).

580J

49

Page 49
Image 49
Bryant manual FAN Performance, 580J*04, Cfm Rpm Bhp