Bryant manual FAN PERFORMANCE cont, 580J*09, Phase, Ton Horizontal Supply, Ton Vertical Supply

Models: 580J

1 86
Download 86 pages 11.72 Kb
Page 57
Image 57
Table 49 – 580J*09

FAN PERFORMANCE (cont.)

Table 49 – 580J*09

 

 

 

3 PHASE

 

8.5 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

Field---Supplied Drive1

 

 

Standard Static Option

 

 

Medium Static Option

2550

497

0.48

579

0.61

651

0.75

717

0.90

777

1.05

2763

524

0.58

602

0.72

671

0.87

735

1.03

794

1.19

2975

551

0.70

626

0.86

693

1.01

754

1.18

812

1.35

3188

580

0.84

651

1.00

716

1.17

775

1.34

831

1.52

3400

609

1.00

677

1.17

 

 

797

1.53

851

1.71

739

1.35

3613

638

1.17

703

1.35

763

1.54

819

1.73

871

1.93

3825

668

1.37

730

1.56

788

1.76

842

1.96

893

2.16

4038

698

1.59

758

1.79

813

2.00

866

2.20

915

2.42

4250

728

1.83

786

2.04

839

2.26

890

2.47

938

2.70

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

High Static Option

 

2550

833

1.21

886

1.38

936

1.56

984

1.74

1029

1.93

2763

849

1.36

900

1.53

950

1.72

996

1.90

1041

2.10

2975

865

1.52

916

1.70

964

1.89

1010

2.09

1054

2.29

3188

883

1.70

933

1.89

980

2.09

1025

2.29

1068

2.50

3400

902

1.90

950

2.10

996

2.30

1041

2.51

1083

2.73

3613

921

2.13

969

2.33

1014

2.54

1057

2.76

1099

2.982

3825

941

2.37

988

2.58

1032

2.80

1075

3.02

1116

3.25

4038

963

2.63

1008

2.86

1051

3.08

1093

3.31

1133

3.55

4250

984

2.92

1029

3.15

1071

3.39

1112

3.63

1152

3.87

 

 

 

 

 

 

 

 

 

 

 

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field--- supplied drive is required.

1.Recommend using field--- supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AF055).

2.Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).

Table 50 – 580J*09

 

 

 

3 PHASE

 

8.5 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Standard Static Option

 

 

 

Medium Static Option

2550

526

0.51

600

0.65

666

0.79

727

0.93

783

1.07

2763

557

0.62

627

0.77

690

0.92

749

1.08

804

1.23

2975

588

0.75

655

0.91

716

1.08

772

1.24

825

1.40

3188

621

0.90

684

1.07

 

 

797

1.42

848

1.60

743

1.25

3400

653

1.06

714

1.25

770

1.44

822

1.62

872

1.81

3613

687

1.25

 

 

798

1.65

849

1.84

897

2.04

744

1.45

3825

720

1.45

775

1.67

827

1.88

876

2.09

922

2.30

4038

 

 

807

1.91

856

2.13

904

2.35

949

2.57

754

1.69

4250

788

1.94

839

2.17

886

2.41

932

2.64

976

2.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

High Static Option

 

2550

836

1.20

886

1.34

934

1.48

979

1.61

1022

1.74

2763

855

1.37

904

1.52

950

1.67

995

1.82

1037

1.97

2975

875

1.56

923

1.72

968

1.88

1012

2.04

1053

2.20

3188

897

1.77

 

 

987

2.11

1030

2.29

1071

2.46

943

1.94

3400

919

1.99

964

2.18

1007

2.36

1049

2.55

1089

2.731

3613

943

2.24

986

2.44

1029

2.63

1069

2.83

1108

3.02

3825

967

2.51

1010

2.71

1051

2.92

1090

3.13

1129

3.34

4038

992

2.80

1034

3.02

1074

3.24

1112

3.46

1150

3.68

4250

1018

3.11

1058

3.34

 

 

---

---

---

---

1097

3.57

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.

1. Recommend using field supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).

580J

57

Page 57
Image 57
Bryant manual FAN PERFORMANCE cont, 580J*09, Phase, Ton Horizontal Supply, Ton Vertical Supply