Bryant 580J manual Legend, Unbalanced 3-PhaseSupply Voltage

Models: 580J

1 86
Download 86 pages 11.72 Kb
Page 68
Image 68
LEGEND:

TABLE 67 (cont.) MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.

580J

LEGEND:

 

 

C.O.

---

Convenience outlet

DISC

---

Disconnect

FLA

---

Full load amps

IFM

---

Indoor fan motor

LRA

---

Locked rotor amps

MCA

---

Minimum circuit amps

MOCP

--- Maximum over current protection

P.E.

---

Power exhaust

UNPWRD CO

---

Un---powered convenient outlet

NOTES:

 

 

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit break- er.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

 

average voltage

 

Example: Supply voltage is 230-3-60

AB = 224 v

BC = 231 v

AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

 

 

3

3

 

 

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

 

227

 

 

 

= 1.76%

 

This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.