CURBS & WEIGHTS DIMENSIONS - 580J 14 (cont.)

580J

C

B

C08528

Fig. 10 - Dimensions 580J-14

D

A

C08337

 

 

 

Fig. 11 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48---

in (1219 mm)

Unit disconnect is mounted on panel

 

36---

in (914 mm)

If dimension--- B is 12--- in (305 mm)

A

18---

in (457 mm)

No disconnect, convenience outlet option

 

18---

in (457 mm)

Recommended service clearance (use electric screwdriver)

 

12---

in (305 mm)

Minimum clearance (use manual ratchet screwdriver)

 

 

 

 

 

36---

in (914 mm)

Unit has economizer

B

12---

in (305 mm)

If dimension--- A is 36--- in (914 mm)

 

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

 

 

 

 

C

36---

in (914 mm)

Side condensate drain is used

18---

in (457 mm)

Minimum clearance

 

 

 

 

 

 

48---

in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42---

in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---

in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

 

 

 

 

24

Page 24
Image 24
Bryant manual Curbs & Weights Dimensions 580J 14, Dimension Condition