TABLE 4ÐICM FIOP PHYSICAL DATAÐUNIT 683B

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 683B

024040

030040

030060

036060

036090

042060

042090

NOMINAL CAPACITY (ton)

2

2-1/2

2-1/2

3

3

3-1/2

3-1/2

OPERATING WEIGHT (lb.)

310

324

324

321

321

380

380

COMPRESSORS

 

 

 

Scroll

 

 

 

Quantity

 

 

 

1

 

 

 

REFRIGERANT (R-410A)

7.0

8.9

8.9

9.3

9.3

9.5

9.5

Quantity (lb.)

 

 

 

 

 

 

 

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

 

Orifice Indoor (in.)

0.061

0.061

0.061

0.067

0.067

0.073

0.073

Check-Flo-Rater™ Piston

 

 

 

 

 

 

 

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

 

Orifice Outdoor (in.)

0.032 (2)

0.040 (2)

0.040 (2)

0.040 (2)

0.040 (2)

0.038 (2)

0.038 (2)

Check-Flo-Rater™ Piston

 

 

 

 

 

 

 

OUTDOOR COIL

2...17

2...17

2...17

2...17

2...17

2...17

2...17

Rows...Fins/in.

8.5

10.3

10.3

10.3

10.3

13.5

13.5

Face Area (sq ft)

 

 

 

 

 

 

 

OUTDOOR FAN

2350

2350

2350

2500

2500

2350

2350

Nominal Cfm

22

22

22

22

22

22

22

Diameter (in.)

1/8 (825)

1/8 (825)

1/8 (825)

1/4 (1100)

1/4 (1100)

1/8 (825)

1/8 (825)

Motor Hp (Rpm)

 

 

 

 

 

 

 

INDOOR COIL

3...15

3...15

3...15

4...15

4...15

3...15

3...15

Rows...Fins/in.

3.7

3.7

3.7

3.7

3.7

4.7

4.7

Face Area (sq ft)

 

 

 

 

 

 

 

INDOOR BLOWER

800

1000

1000

1200

1200

1400

1400

Nominal Airflow (Cfm)

10 X 10

10 X 10

10 X 10

11 X 10

11 X 10

11 X 10

11 X 10

Size (in.)

1/2

1/2

1/2

3/4

3/4

3/4

3/4

Motor (HP)

 

 

 

 

 

 

 

FURNACE SECTION*

 

 

 

 

 

 

 

Burner Orifice No. (Qty...Drill Size)

2...44

2...44

2...38

2...38

3...38

2...38

3...38

Natural Gas

2...50

2...50

2...46

2...46

3...46

2...46

3...46

Burner Orifice No. (Qty...Drill Size)

 

 

 

 

 

 

 

Propane Gas

 

 

 

 

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

 

 

610 ± 15

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

420 ± 25

 

 

 

Reset (Auto)

 

 

 

 

 

 

 

 

 

 

 

 

 

LOSS-OF-CHARGE/LOW-

 

 

 

 

 

 

 

PRESSURE SWITCH

 

 

 

20 ± 5

 

 

 

(Liquid Line) (psig)

 

 

 

 

 

 

 

 

 

45 ± 10

 

 

 

Cutout

 

 

 

 

 

 

 

 

 

 

 

 

 

Reset (Auto)

 

 

 

 

 

 

 

RETURN-AIR FILTERS (in.)

20 X 20 X 1

20 X 20 X 1

20 X 20 X 1

20 X 24 X 1

20 X 24 X 1

24 X 30 X 1

24 X 30 X 1

Throwaway

 

 

 

 

 

 

 

* Based on altitude of 0 to 2000 ft.

Ð15Ð

Page 15
Image 15
Bryant 602B, 583B, 702B installation instructions ÐICM FIOP PHYSICAL DATAÐUNIT 683B, Ð15Ð

602B, 683B, 702B, 583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.