TABLE 5ÐICM FIOP PHYSICAL DATAÐUNIT 683B (CONTINUED)

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 683B

048090

048115

048130

 

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

 

5

5

5

OPERATING WEIGHT (lb.)

409

409

409

 

504

504

504

COMPRESSORS

 

 

Scroll

 

 

Quantity

 

 

 

1

 

 

REFRIGERANT (R-410A)

10.6

10.6

10.6

 

12.4

12.4

12.4

Quantity (lb.)

 

 

 

 

 

 

 

 

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

 

Orifice Indoor (in.)

.076

.076

.076

 

.088

.088

.088

Check-Flo-Rater™ Piston

 

 

 

 

 

 

 

REFRIGERANT METERING DEVICE

 

 

 

 

 

 

 

Orifice Outdoor (in.)

0.046 (2)

0.046 (2)

0.046 (2)

 

0.052 (2)

0.052 (2)

0.052 (2)

Check-Flo-Rater™ Piston

 

 

 

 

 

 

 

OUTDOOR COIL

2...17

2...17

2...17

 

2...17

2...17

2...17

Rows...Fins/in.

 

13.5

13.5

13.5

 

15.4

15.4

15.4

Face Area (sq ft)

 

 

 

 

 

 

 

 

OUTDOOR FAN

3300

3300

3300

 

3300

3300

3300

Nominal Cfm

 

22

22

22

 

22

22

22

Diameter (in.)

 

1/4 (1100)

1/4 (1100)

1/4 (1100)

 

1/4 (1100)

1/4 (1100)

1/4 (1100)

Motor Hp (Rpm)

 

 

 

 

 

 

 

 

INDOOR COIL

4...15

4...15

4...15

 

4...15

4...15

4...15

Rows...Fins/in.

 

4.7

4.7

4.7

 

5.7

5.7

5.7

Face Area (sq ft)

 

 

 

 

 

 

 

 

INDOOR BLOWER

1600

1600

1600

 

1750

1750

1750

Nominal Airflow (Cfm)

 

11 X 10

11 X 10

11 X 10

 

11 X 10

11 X 10

11 X 10

Size (in.)

 

3/4

3/4

3/4

 

1.0

1.0

1.0

Motor (HP)

 

 

 

 

 

 

 

 

FURNACE SECTION*

 

 

 

 

 

 

 

Burner Orifice No. (Qty...Drill Size)

3...38

3...33

3...31

 

3...38

3...33

3...31

Natural Gas

 

3...46

3...42

3...41

 

3...46

3...42

3...41

Burner Orifice No. (Qty...Drill Size)

 

 

 

 

 

 

 

 

Propane Gas

 

 

 

 

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

 

610 ± 15

 

 

Cutout

 

 

 

 

 

 

420 ± 25

 

 

Reset (Auto)

 

 

 

 

 

 

 

 

 

 

 

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

 

 

 

 

 

 

 

(Liquid Line) (psig)

 

 

20 ± 5

 

 

Cutout

 

 

45 ± 10

 

 

Reset (Auto)

 

 

 

 

 

 

 

RETURN-AIR FILTERS (in.)

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

 

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

Throwaway

 

 

 

 

 

 

 

 

* Based on altitude of 0 to 2000 ft.

TABLE 6Ð683B WITH ICM FIOP ELECTRICAL DATA

 

 

VOLTAGE

COMPRESSOR

OUTDOOR FAN

INDOOR FAN

POWER SUPPLY

UNIT

 

RANGE

MOTOR

MOTOR

V-PH-HZ

 

 

 

 

SIZE 683B

MIN

MAX

RLA

LRA

FLA

FLA

MCA

MAX FUSE

 

 

 

OR CKT. BKR.

 

 

 

 

 

 

 

 

 

024

208/230±1±60

187

253

13.5

61.0

0.9

4.3

22.1

30

030

208/230±1±60

187

253

15.9

73.0

0.9

4.3

25.1

35

036

208/230±1±60

187

253

16.9

83.0

1.6

6.8

29.5

40

042

208/230±1±60

187

253

22.4

105.0

0.9

6.8

35.7

50

048

208/230±1±60

187

253

21.3

109.0

1.6

6.8

35.0

50

060

208/230±1±60

187

253

27.6

158.0

1.6

9.2

45.3

60

 

 

 

 

 

 

 

 

 

 

Ð16Ð

Page 16
Image 16
Bryant 583B, 702B, 602B ÐICM FIOP PHYSICAL DATAÐUNIT 683B CONTINUED, Ð683B WITH ICM FIOP ELECTRICAL DATA, Ð16Ð

602B, 683B, 702B, 583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.