HIGH VOLTAGE |
| |
POWER LEADS | POWER | |
(SEE UNIT WIRING | ||
SUPPLY | ||
LABEL) | ||
| ||
GND | ||
FUSED DISCONNECT |
Factory selected gas heat size should correspond to unit label.
b. AC/HP SIZEÐSELECT SYSTEM SIZE INSTALLED |
Factory selected air conditioner size should correspond to |
capacity of unit installed. Installer should verify air conditioner |
size to ensure that airflow delivered falls within proper range |
for the size unit installed. This applies to all operational modes. |
c. SYSTEM TYPEÐSELECT SYSTEM TYPE INSTALLED |
Factory selected on 583B for |
For Gas Heat/Electric Cool Unit±AC must be selected. |
CONTROL BOX
| BLK(DH) |
| YEL(Y) |
| GRN(G) |
RED(R) | |
POWER LEADS | |
(SEE UNIT | BRN(C) |
WIRING LABEL) | |
| WHI(W1) |
| GRA(W2) |
DHUM
Y
G
R
C
W1
W2
THERMOSTAT (TYPICAL)
d. AC/HP CFM ADJUSTÐSELECT NOMINAL, LOW, OR |
HIGH AIRFLOW |
The AC/HP CFM Adjust select is factory set to the |
(NOM for 060) tap. The CFM Adjust selections NOM/LO will |
regulate airflow supplied for all operational modes, except |
over nominal unit size selected and LO provides 10 percent |
airflow below nominal unit size selected. Adjust selection |
options are provided to adjust airflow supplied to meet indi- |
vidual installation needs for such things as noise, comfort, and |
humidity removal (See Fig. 8, D as indicated). |
SPLICE BOX
LEGEND
Field
Field
C01027
Connections
HIGH VOLTAGE |
| |
POWER LEADS | POWER | |
(SEE UNIT WIRING | ||
SUPPLY | ||
LABEL) | ||
| ||
GND | ||
FUSED DISCONNECT |
e. ON/OFF DELAYÐSELECT DESIRED |
TIME DELAY PROFILE |
Four motor operation delay profiles are provided to customize |
and enhance system operation (See Fig. 8, E as indicated). |
Selection options are: |
(1.) The standard 90 sec off delay (Factory Setting) at 100 |
percent airflow in cooling mode. In heating mode, IGC |
will control 45 sec on delay with no airflow and 45 sec off |
delay. |
(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at |
100 percent airflow profile is used when it is desirable to |
allow system coils time to |
the airflow in heating mode. |
(3.) A no delay option used for servicing unit or when a |
thermostat is utilized to perform delay functions in cooling |
mode. In heating mode IGC will control 45 sec on delay |
with no airflow and 45 sec off delay. |
CONTROL BOX
| BLK(DH) |
| YEL(Y) |
| GRN(G) |
RED(R) | |
POWER LEADS | |
(SEE UNIT | BRN(C) |
WIRING LABEL) | |
| WHI(W1) |
| GRA(W2) |
| ORN(0) |
DHUM
Y
G
R
C
W1
W2
O
THERMOSTAT (TYPICAL)
(4.) Not recommended for 583B | |
f. CONTINUOUS FANÐSELECT DESIRED FAN SPEED | |
WHEN THERMOSTAT IS SET ON CONTINUOUS FAN | |
(1.) | LO speedÐFactory setting, 50 percent cooling mode |
| airflow. |
(2.) | MED speedÐMove connector to MED, 65 percent cooling |
| mode airflow. |
(3.) | HI speedÐMove connector to HI, 100 percent cooling |
| mode airflow (See Fig. 8, F as indicated). |
g. |
SPLICE BOX
LEGEND
Field
Field
C01028
Connections
The unit must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used (See Fig. 8).
a. GAS HEAT/CFMÐSELECT GAS HEAT INPUT SIZE
Ð3Ð
The | |
automotive fuse placed in series with the transformer SEC2 and | |
the R circuit. The C circuit of the transformer is referenced to | |
chassis ground through a printed circuit run at SEC1 connected | |
to metal standoff marked with ground symbol. | |
h. BASIC UNIT CONFIGURATION | |
The following basic configuration of the indoor motor will | |
provide ARI rated performance of the 583B. This BASIC | |
CONFIGURATION should be used when the rated ARI perfor- | |
mance is required, or if system enhancements such as super | |
dehumidify are not needed. | |
(1.) | |
(2.) | AC/HP |
| verify. |