WARNING: Before performing service or maintenance operations on system, turn off main power to unit and install
CAUTION: Puron®
WARNING: Make sure that the power supply to the unit is switched OFF before making any wiring changes. With disconnect switch open, move yellow wire from trans- former (3/16 in.) terminal marked 230 to terminal marked
200.This retaps transformer to primary voltage of
HIGH VOLTAGE |
| |
POWER LEADS | POWER | |
(SEE UNIT WIRING | ||
SUPPLY | ||
LABEL) | ||
|
GND | |
FUSED DISCONNECT |
NOTE: The minimum outdoor cooling operating temperature for units using this ICM motor option is 55°F. To operate in cooling at lower ambients the Motor Master™ II low ambient kit is required.
These instructions cover the installation of a Bryant Small Pack- aged Product with ICM
CONTROL BOX
| BLK(DH) |
| YEL(Y) |
| GRN(G) |
RED(R) | |
POWER LEADS | |
(SEE UNIT | BRN(C) |
WIRING LABEL) | |
| WHI(W1) |
DHUM
Y
G
R
C
W1
THERMOSTAT (TYPICAL)
Refer to unit Installation Instructions.
I.ELECTRICAL CONNECTIONS
NOTE: Do not use any type of
Use no. 18 American Wire Gage (AWG)
SPLICE BOX
LEGEND
Field
Field
C01026
Connections
HIGH VOLTAGE |
| |
POWER LEADS | POWER | |
(SEE UNIT WIRING | ||
SUPPLY | ||
LABEL) | ||
| ||
| ||
| FUSED DISCONNECT | |
| GND |
between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG
Remove knockout hole located in the heat section panel adjacent to the service access panel (See unit installation package). Remove the rubber grommet from the installer's packet (included with unit) and install grommet in the knockout opening. Provide a drip loop
CONTROL BOX |
|
| BLK (DH) |
| WHT(W1) |
| YEL(Y) |
GRN(G) | |
POWER LEADS | |
(SEE UNIT | RED(R) |
WIRING LABEL) | |
| BRN(C) |
| ORN(O) |
DHUM
W/W1
Y/Y2
G
R
C
O/W2
THERMOSTAT (THERMIDISTAT ™ )
before running wire through panel. Run the
SPECIAL PROCEDURES FOR 208±V OPERATION
Ð2Ð
SPLICE BOX
FIELD CONTROL - VOLTAGE WIRING
FIELD HIGH - VOLTAGE WIRING
C01107
Connections
EASY SELECT™ CONFIGURATION TAPS FOR 583B Easy Select™ taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a