Bryant 683B C. Easy SelectÐ583B, Introduction, Receiving And Installation, B. Standard Connection

Models: 602B 683B 702B 583B

1 30
Download 30 pages 37.07 Kb
Page 2
Image 2

WARNING: Before performing service or maintenance operations on system, turn off main power to unit and install lock-out tag. Turn off accessory heater power switch if applicable. Electrical shock could cause severe injury or death.

CAUTION: Puron® (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron® (R-410A) equipment. Ensure service equipment is rated for Puron® (R-410A)

WARNING: Make sure that the power supply to the unit is switched OFF before making any wiring changes. With disconnect switch open, move yellow wire from trans- former (3/16 in.) terminal marked 230 to terminal marked

200.This retaps transformer to primary voltage of 208-v. Electrical shock could cause serious injury or death.

C.Easy Select™Ð583B

HIGH VOLTAGE

 

POWER LEADS

POWER

(SEE UNIT WIRING

SUPPLY

LABEL)

 

INTRODUCTION

GND

FIELD-SUPPLIED

FUSED DISCONNECT

NOTE: The minimum outdoor cooling operating temperature for units using this ICM motor option is 55°F. To operate in cooling at lower ambients the Motor Master™ II low ambient kit is required.

These instructions cover the installation of a Bryant Small Pack- aged Product with ICM motor-factory installed option (FIOP). This option can be selected as a FIOP on gas heating/electric cooling (583B), dual fuel±electric heat pump with gas heat back-up (683B), electric cooling (702B) or electric heat pump (602B) units with Puron®.

CONTROL BOX

 

BLK(DH)

 

YEL(Y)

 

GRN(G)

LOW-VOLTAGE

RED(R)

POWER LEADS

(SEE UNIT

BRN(C)

WIRING LABEL)

 

WHI(W1)

DHUM

Y

G

R

C

W1

THERMOSTAT (TYPICAL)

RECEIVING AND INSTALLATION

Refer to unit Installation Instructions.

ICM FIOP PRE-START-UP

I.ELECTRICAL CONNECTIONS

A.Control Voltage Connections

NOTE: Do not use any type of power-stealing thermostat, with- out connecting the C (Common) terminal. Failure to follow this note could result in unit control problems.

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control voltage connections

SPLICE BOX

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

C01026

Fig. 2Ð583B High- and Control-Voltage

Connections

HIGH VOLTAGE

 

POWER LEADS

POWER

(SEE UNIT WIRING

SUPPLY

LABEL)

 

 

FIELD-SUPPLIED

 

FUSED DISCONNECT

 

GND

between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35 C minimum) wires.

B.Standard Connection

Remove knockout hole located in the heat section panel adjacent to the service access panel (See unit installation package). Remove the rubber grommet from the installer's packet (included with unit) and install grommet in the knockout opening. Provide a drip loop

CONTROL BOX

 

 

BLK (DH)

 

WHT(W1)

 

YEL(Y)

LOW-VOLTAGE

GRN(G)

POWER LEADS

(SEE UNIT

RED(R)

WIRING LABEL)

 

BRN(C)

 

ORN(O)

DHUM

W/W1

Y/Y2

G

R

C

O/W2

THERMOSTAT (THERMIDISTAT ™ )

before running wire through panel. Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box. Locate 18-gage wires leaving control box. These low-voltage connection leads can be identified by colors (See Fig. 2, 3, 4 or 5). Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Route leads through hole in bottom of control box and make low-voltage connections (See Fig. 2, 3, 4 or 5). Secure all cut wires, so that they do not interfere with operation of unit.

SPECIAL PROCEDURES FOR 208±V OPERATION

Ð2Ð

SPLICE BOX

FIELD CONTROL - VOLTAGE WIRING

FIELD HIGH - VOLTAGE WIRING

C01107

Fig. 3Ð683B High- and Control-Voltage

Connections

EASY SELECT™ CONFIGURATION TAPS FOR 583B Easy Select™ taps are used by the installer to configure a system. The ICM motor uses the selected taps to modify its operation to a

Page 2
Image 2
Bryant 683B C. Easy SelectÐ583B, Introduction, Receiving And Installation, Icm Fiop Pre-Start-Up I. Electrical Connections