REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm) Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . | . . . . . . . 36 (914) |
Unit top | . . . . . . . 48 (1219) |
Side opposite ducts | . . . . . . . 36 (914) |
Duct panel | . . . . . . 12 (304.8)* |
Flue Panel | . . . . . . . .36 (914.4) |
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
LEGEND
CG - Center of Gravity COND - Condenser EVAP - Evaporator
NEC - National Electrical Code REQ'D - Required
Note: Dimensions are in in. (mm)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8) Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
NEC REQ’D CLEARANCES. in. (mm) |
|
|
| |
|
|
|
|
|
Between units, power entry side | . . | . 42 | (1066.8) | |
Unit and ungrounded surfaces, power entry side | . | . . . 36 (914) | ||
Unit and block or concrete walls and other grounded |
|
|
| |
surfaces, control box side | . . | . 42 | (1066.8) |
C99017
| ELECTRICAL | UNIT WEIGHT | UNIT HEIGHT | CENTER OF GRAVITY | ||||
UNIT | IN. (MM) |
| IN. (MM) |
| ||||
CHARACTERISTICS |
|
|
|
| ||||
| lb. | kg. | "A" | X | Y | Z | ||
|
| |||||||
583B030040/060 | 313.0 | 142.0 | 39.02 (991.1) | 22.0 (558.8) | 15.3 (387.4) | 17.6 (447.0) | ||
583B036060/090 | 321.0 | 145.6 | 35.02 (889.5) | 22.0 (558.8) | 15.3 (387.4) | 16.5 (419.1) | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|