Bryant instruction manual 583B042-060Unit Dimensions

Models: 583B

1 30
Download 30 pages 21.04 Kb
Page 6
Image 6
Fig. 7—583B042-060 Unit Dimensions

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

 

in. [mm]

 

EVAP. COIL ACCESS SIDE

36.00

[914.0]

 

POWER ENTRY SIDE

36.00

[914.0]

 

(EXCEPT FOR NEC REQUIREMENTS)

 

 

 

UNIT TOP

36.00

[914.0]

 

SIDE OPPOSITE DUCTS

36.00

[914.0]

 

DUCT PANEL

12.00

[304.8]

*

FLUE HEAT PANEL

36.00 [914.4]

 

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM

 

WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

 

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

 

in. [mm]

TOP OF UNIT

14.00

[355.6]

DUCT SIDE OF UNIT

2.00

[50.8]

SIDE OPPOSITE DUCTS

14.00

[355.6]

BOTTOM OF UNIT

0.50

[12.7]

NEC. REQUIRED CLEARANCES.

 

in. [mm.]

BETWEEN UNITS, POWER ENTRY SIDE

42.00 [1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...

36.00 [914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

 

GROUNDED SURFACES, POWER ENTRY SIDE

42.00 [1066.8]

FLUE HOOD

C99074

 

ELECTRICAL

UNIT WEIGHT

UNIT HEIGHT

CENTER OF GRAVITY

UNIT

IN. (MM)

 

IN. (MM)

 

CHARACTERISTICS

 

 

 

 

 

lb.

kg.

"A"

X

Y

Z

 

 

583B042060/090

208/230-3-60

382

173.3

38.98 (990.2)

23.0 (584.2)

16.3 (412.8)

16.6 (421.6)

460-3-60

 

 

 

 

 

 

 

583B048090/115/130

208/230-3-60

421

191.0

38.98 (990.2)

21.5 (546.1)

16.6 (422.1)

18.0 (457.2)

460-3-60

 

 

 

 

 

 

 

583B060090/115/130

208/230-3-60,

468

212.3

42.98 (1091.7)

23.5 (596.9)

16.3 (412.8)

17.6 (447.0)

460-3-60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7—583B042-060 Unit Dimensions

—6—

Page 6
Image 6
Bryant instruction manual 583B042-060Unit Dimensions