REQUIRED CLEARANCE FOR OPERATION AND SERVICING
| in. [mm] |
| |
EVAP. COIL ACCESS SIDE | 36.00 | [914.0] |
|
POWER ENTRY SIDE | 36.00 | [914.0] |
|
(EXCEPT FOR NEC REQUIREMENTS) |
|
|
|
UNIT TOP | 36.00 | [914.0] |
|
SIDE OPPOSITE DUCTS | 36.00 | [914.0] |
|
DUCT PANEL | 12.00 | [304.8] | * |
FLUE HEAT PANEL | 36.00 [914.4] |
| |
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM |
| ||
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE. |
|
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
| in. [mm] | |
TOP OF UNIT | 14.00 | [355.6] |
DUCT SIDE OF UNIT | 2.00 | [50.8] |
SIDE OPPOSITE DUCTS | 14.00 | [355.6] |
BOTTOM OF UNIT | 0.50 | [12.7] |
NEC. REQUIRED CLEARANCES.
| in. [mm.] |
BETWEEN UNITS, POWER ENTRY SIDE | 42.00 [1066.8] |
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ... | 36.00 [914.0] |
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER |
|
GROUNDED SURFACES, POWER ENTRY SIDE | 42.00 [1066.8] |
FLUE HOOD
C99074
| ELECTRICAL | UNIT WEIGHT | UNIT HEIGHT | CENTER OF GRAVITY | ||||
UNIT | IN. (MM) |
| IN. (MM) |
| ||||
CHARACTERISTICS |
|
|
|
| ||||
| lb. | kg. | "A" | X | Y | Z | ||
|
| |||||||
583B042060/090 | 382 | 173.3 | 38.98 (990.2) | 23.0 (584.2) | 16.3 (412.8) | 16.6 (421.6) | ||
|
|
|
|
|
|
| ||
583B048090/115/130 | 421 | 191.0 | 38.98 (990.2) | 21.5 (546.1) | 16.6 (422.1) | 18.0 (457.2) | ||
|
|
|
|
|
|
| ||
583B060090/115/130 | 468 | 212.3 | 42.98 (1091.7) | 23.5 (596.9) | 16.3 (412.8) | 17.6 (447.0) | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|