Bryant 583B SuggestedRigging, CondensateTrap VII. INSTALL FLUE HOOD, SedimentTrap

Models: 583B

1 30
Download 30 pages 21.04 Kb
Page 7
Image 7
Fig. 8—Suggested Rigging

DETAIL A

A05179

UNIT 583B

MAXIMUM WEIGHT

A

 

 

B

SIZE

lb

kg

in.

 

mm

in.

mm

030

335

152

22.0

 

558.5

15.3

388.6

036

343

156

22.0

 

558.5

15.3

388.6

042

404

183

23.0

 

584.2

16.3

414.0

048

443

201

21.5

 

546.1

16.3

414.0

060

490

222

23.5

 

596.9

16.3

414.3

Fig. 8—Suggested Rigging

If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage. See Fig. 9. Make sure that the outlet of the trap is at least 1 in. lower than the drain pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.

1” (25mm) MIN.

TRAP

OUTLET

2” (50mm) MIN.

C99013

Fig. 9—Condensate Trap

VII. INSTALL FLUE HOOD

The flue hood assembly is shipped screwed to the coil panel in the indoor blower compartment. Remove the service access panel to locate the assembly.

CAUTION: The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicated in this section of the unit installation instruc- tions.

NOTE: Dedicated low NOx models MUST be installed in Cali- fornia Air Quality Management Districts where a Low NOx rule exists.

—7—

IN

TEE

OUTFig. 9—Condensate Trap

NIPPLE

3˝ MIN

CAP

C99020

Fig. 10—Sediment Trap

These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory.

NOTE: Low NOx requirements apply only to natural gas instal- lations.

Install the flue hood as follows:

1.This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or NFPA (National Fire Protection Association) latest revi- sion. Refer to Provincial and local plumbing or waste water codes and other applicable local codes.

2.Remove flue hood from shipping location (inside the blower compartment). Place vent cap assembly over flue panel. Orient screw holes in vent cap with holes in the flue panel.

Page 7
Image 7
Bryant 583B instruction manual SuggestedRigging, CondensateTrap VII. INSTALL FLUE HOOD, SedimentTrap