INSTALLATION

Distance (ft.)

Number of Pipe Supports

16

2

32

3

48

5

64

7

80

9

C.3.1. Installation At The Same Level

If the condensing unit is going to be installed at the same level with the cabinet, follow the instructions in the FIG #5

FIG # 5

C.3.2. Installation At Different Levels

If the remote condensing unit is installed at a higher level than the cabinet (FIG #6) insert a siphon in the return line at every 6 ft. of difference in height. If the remote condensing unit is installed at a lower level than the cabinet (FIG #7) it is not necessary to insert any siphons.

 

FIG #6

FIG #7

Insert a siphon at the beginning (a) and at the end (b) of each riser

 

 

 

 