Burnham 8H manual VIII. System Start-Up

Models: 8H

1 92
Download 92 pages 19.18 Kb
Page 52
Image 52

VIII. System Start-Up

 

 

WARNING

9.

Close purge valve, continue filling the system

 

 

 

 

until the pressure gauge reads the desired cold fill

Completely read, understand and follow all

 

 

pressure. Close fill valve.

 

instructions in this manual before attempting

 

 

(Note - If make-up water line is equipped with

start-up.

 

 

pressure reducing valve, adjust pressure reducing

A. Safe operation and other performance criteria were met

 

 

valve to desired cold fill pressure. Follow fill valve

 

 

manufacturer’s instructions).

 

 

with the gas manifold and control assembly provided

 

 

 

 

10.

Open isolation valve in boiler supply piping.

 

on boiler when boiler underwent tests specified in

 

American National Standard for Gas-Fired Low-

11.

Remove hose from purge valve.

 

 

Pressure Steam and Hot Water Boilers, ANSI Z21.13.

 

F. Confirm that the boiler and system have no water

B.

 

 

 

Check Main Burners. Main burners must be properly

 

leaks.

 

 

 

 

located on support bracket in Base Rear Panel, seated

 

G. Prepare to check operation.

 

 

on Main Burner Orifices, and secured with hitch pin

 

 

 

1.

Obtain gas heating value (in Btu per cubic foot)

 

clips.

C. Verify that the venting, water piping, gas piping

 

 

from gas supplier.

 

2.

Connect manometer to pressure tap on gas valve.

 

and electrical system are installed properly. Refer to

 

 

 

Use 1/8 NPT tapping provided.

 

 

installation instructions contained in this manual.

 

 

 

 

3.

Temporarily turn off all other gas-fired appliances.

D. Confirm all electrical, water and gas supplies

4.

Turn on gas supply to the boiler gas piping.

 

are turned off at the source and that vent is clear of

 

obstructions.

5.

Confirm that the supply pressure to the gas valve is

E. FILL ENTIRE HEATING SYSTEM WITH WATER

 

 

14 in. w.c. or less.

 

6.

Open the field installed manual gas shut-off valve

 

and vent air from system. Use following procedure on

 

a Series Loop or multi-zoned system installed as per

 

 

located upstream of the gas valve on the boiler.

 

Figure 23 to remove air from system when filling.

7.

Using soap solution, or similar non-combustible

 

 

 

 

 

solution, electronic leak detector or other approved

 

 

WARNING

 

 

 

 

 

 

method. Check that boiler gas piping, valves, and

 

 

 

 

 

all other components are leak free. Eliminate any

The maximum operating pressure of this boiler is

 

 

 

 

leaks.

 

 

 

50 psig. Never exceed this pressure. Do not plug

 

 

 

 

 

8.

Purge gas line of air.

 

or modify pressure relief valve.

 

 

1. Close full port ball valve in boiler supply piping.

 

H. Follow Lighting or Operating Instructions to place

 

 

boiler in operation. Refer to label on inside of Front

 

2. Isolate all zones by closing zone valves or shut-off

 

 

 

Removable Panel or appropriate Figure as listed in

 

 

valves in supply and return of each zone(s).

 

Table 11.

 

 

 

 

3. Attach a hose to the vertical purge valve located

 

 

 

 

 

 

 

 

 

 

DANGER

 

 

 

 

prior to the full port ball valve in the system supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

piping. (Note - Terminate hose in five gallon bucket

 

 

 

 

 

 

 

 

 

Do not use matches, candles, open flames or

 

 

at a suitable floor drain or outdoor area).

 

 

 

 

other ignition source to check for leaks.

 

4. Starting with one circuit at a time, open zone valve

 

 

 

 

 

 

 

 

 

 

or shut-off valve in system supply and return piping.

 

Table 11: Lighting and Operating Instructions

 

5.

Open purge valve.

 

 

 

 

 

 

 

 

 

6.

Open fill valve (Make-up water line should be

 

 

 

Lighting or

Pilot Flame

 

 

Ignition System

Operating

 

 

located directly after full port ball valve in system

 

Illustration

 

 

 

 

 

Instructions

 

 

supply piping between air scoop and expansion

 

 

 

 

 

 

 

Standing Pilot (24)

Figure 43

Figure 48

 

 

tank).

 

 

7. Allow water to overflow from bucket until discharge

 

Honeywell EI

Figure 44

Figure 49

 

 

 

OP

Figure 45

Figure 50

 

 

from hose is bubble free for 30 seconds.

 

 

 

8. Close the open zone valve or shut-off valve for the

 

 

EP

Figure 46

Figure 51

 

 

OP-CSD-1

 

 

Figure 50

 

 

zone being purged of air, then open the zone valve

 

Figure 47

 

 

 

EP-CSD-1

Figure 51

 

 

or shut-off valve for the next zone to be purged.

 

 

 

 

 

Repeat this step until all zones have been purged. At

 

 

 

 

 

 

52completion, open all zone valves or shut-off valves.

Page 52
Image 52
Burnham 8H manual VIII. System Start-Up