Honeywell EI Ignition Module Yellow LED Flame Codes
Yellow LED | Indicates | Recommended Service Action | |
Flash Codea | |||
|
|
| |
Heartbeat | Normal Flame Signal | N/A | |
|
|
| |
| Weak Flame Signal - |
| |
| System will operate reliably but flame signal is less than | Perform routine maintenance to | |
2 | desired. | ||
assure optimum flame signal. | |||
| Note: This indication may flash temporarily during or | ||
|
| ||
| shortly after lightoff on some applications. |
| |
|
|
| |
| Marginal Flame Signal (less than 1.1 µA) - |
| |
| System may not operate reliably over time. Service call | Check gas supply, pilot burner, flame | |
1 | recommended. | sense wiring, contamination of flame rod, | |
| Note: This indication may flash temporarily during or | burner ground connection. | |
| shortly after lightoff on some applications. |
| |
OFF | No Flame or Flame Signal - | N/A | |
below minimum threshold for system operation. | |||
|
| ||
|
|
| |
aFlash Code Descriptions |
|
-Heartbeat: Constant ½ second bright, ½ second dim cycles.
-The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats sequence.
64