Carrier 30HW018-040, 30HL050, 30HK040-060 Ð Troubleshooting, Compressor cycles control

Models: 30HK040-060 060 30HL050 30HW018-040

1 44
Download 44 pages 26.67 Kb
Page 38
Image 38
Table 14 Ð Troubleshooting

COOLING LOAD SATISFIED Ð Unit shuts down if cool- ing load is satis®ed. Unit restarts if required after comple- tion of 5-minute timer cycle.

THERMISTOR FAILURE Ð If thermistor fails in open mode, the temperature controller shuts down the unit in an out-of- range condition. Replace the thermistor. Unit restarts auto- matically after completion of a 5-minute timer cycle, and when the leaving cooler chilled ¯uid temperature rises above the upper deadband limit of the temperature controller.

NOTE: If the thermistor fails in closed mode, the tempera- ture controller keeps trying to load up.

If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart.

Table 14 Ð Troubleshooting

SYMPTOMS

CAUSE

REMEDY

Compressor does

Power line open

Reset circuit breaker.

not run

 

 

Control fuse or circuit breaker opens

Check control circuit for ground or short. Reset breaker

 

 

and replace fuse.

 

Compressor overtemperature sensor open

Find cause of high temperature and reset controls.

 

Tripped power breaker

Check the controls. Find the cause of trip and

 

 

reset breaker.

 

Condenser circulating pump not running

Power off Ð restart.

 

 

Pump binding Ð free pump.

 

 

Incorrect wiring Ð rewire.

 

 

Pump motor burned out Ð replace.

 

Loose terminal connection

Check connections.

 

Improperly wired controls

Check wiring and rewire if necessary.

 

Low line voltage

Check line voltage Ð determine location of voltage drop

 

 

and remedy de®ciency.

 

Compressor motor defective

Check motor winding for open or short. Replace

 

 

compressor if necessary.

 

Seized compressor

Replace compressor.

Compressor cycles

Loss of charge control erratic in action

Repair leak and recharge.

off on loss of

 

 

 

Replace control.

charge

 

Low refrigerant charge

Add refrigerant.

 

 

Low suction temperature

Raise cooler leaving ¯uid temperature set point.

 

Compressor suction valve leaking

Replace valve plate.

 

Plugged compressor suction strainer

Clean or replace strainer.

 

Compressor suction shutoff valve partially closed

Open valve.

Compressor cycles

Thermistor failure

Replace thermistor.

off on out of range

 

 

System load was reduced faster than

Unit will restart after ¯uid temperature rises back into the

condition

controller could remove stages

control band. Avoid rapidly removing system load.

 

Compressor cycles control

Temperature controller deadband setting is

Raise deadband setting.

steps rapidly

too low

 

Compressor shuts

High-pressure control acting erratically

Replace control.

down on high-

 

 

Compressor discharge valve partially closed

Open valve or replace (if defective).

pressure control

Air in system

Purge system.

 

 

Condenser scaled/dirty

Clean condenser.

 

Receiver not properly vented Ð refrigerant

Repipe as required to provide adequate venting.

 

backs up into evaporator condenser

 

 

Condenser water pump or fans not operating

Start pump Ð repair or replace if defective.

 

System overcharged with refrigerant

Reduce charge.

Unit operates too long

Low refrigerant charge

Add refrigerant.

or continuously

 

 

Control contacts fused

Replace control.

 

 

Air in system

Purge system.

 

Partially plugged or plugged expansion valve

Clean or replace as needed.

 

or ®lter drier

 

 

Defective insulation

Replace or repair as needed.

 

Service load

Keep doors and windows closed.

 

Inefficient compressor

Check valves, and replace if necessary.

Unusual or loud system

Piping vibration

Support piping as required.

noises

 

 

 

Check for loose pipe connections.

 

 

 

Expansion valve hissing

Add refrigerant.

 

 

Check for plugged liquid line ®lter drier.

 

Compressor noisy

Check valve plates for valve noise.

 

 

Replace compressor (worn bearings).

 

 

Check for loose compressor holddown bolts.

 

 

 

38