COOLING LOAD SATISFIED Ð Unit shuts down if cool- ing load is satis®ed. Unit restarts if required after comple- tion of
THERMISTOR FAILURE Ð If thermistor fails in open mode, the temperature controller shuts down the unit in an
NOTE: If the thermistor fails in closed mode, the tempera- ture controller keeps trying to load up.
If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart.
Table 14 Ð Troubleshooting
SYMPTOMS | CAUSE | REMEDY | |
Compressor does | Power line open | Reset circuit breaker. | |
not run |
|
| |
Control fuse or circuit breaker opens | Check control circuit for ground or short. Reset breaker | ||
|
| and replace fuse. | |
| Compressor overtemperature sensor open | Find cause of high temperature and reset controls. | |
| Tripped power breaker | Check the controls. Find the cause of trip and | |
|
| reset breaker. | |
| Condenser circulating pump not running | Power off Ð restart. | |
|
| Pump binding Ð free pump. | |
|
| Incorrect wiring Ð rewire. | |
|
| Pump motor burned out Ð replace. | |
| Loose terminal connection | Check connections. | |
| Improperly wired controls | Check wiring and rewire if necessary. | |
| Low line voltage | Check line voltage Ð determine location of voltage drop | |
|
| and remedy de®ciency. | |
| Compressor motor defective | Check motor winding for open or short. Replace | |
|
| compressor if necessary. | |
| Seized compressor | Replace compressor. | |
Compressor cycles | Loss of charge control erratic in action | Repair leak and recharge. | |
off on loss of |
|
| |
| Replace control. | ||
charge |
| ||
Low refrigerant charge | Add refrigerant. | ||
| |||
| Low suction temperature | Raise cooler leaving ¯uid temperature set point. | |
| Compressor suction valve leaking | Replace valve plate. | |
| Plugged compressor suction strainer | Clean or replace strainer. | |
| Compressor suction shutoff valve partially closed | Open valve. | |
Compressor cycles | Thermistor failure | Replace thermistor. | |
off on out of range |
|
| |
System load was reduced faster than | Unit will restart after ¯uid temperature rises back into the | ||
condition | |||
controller could remove stages | control band. Avoid rapidly removing system load. | ||
| |||
Compressor cycles control | Temperature controller deadband setting is | Raise deadband setting. | |
steps rapidly | too low |
| |
Compressor shuts | Replace control. | ||
down on high- |
|
| |
Compressor discharge valve partially closed | Open valve or replace (if defective). | ||
pressure control | |||
Air in system | Purge system. | ||
| |||
| Condenser scaled/dirty | Clean condenser. | |
| Receiver not properly vented Ð refrigerant | Repipe as required to provide adequate venting. | |
| backs up into evaporator condenser |
| |
| Condenser water pump or fans not operating | Start pump Ð repair or replace if defective. | |
| System overcharged with refrigerant | Reduce charge. | |
Unit operates too long | Low refrigerant charge | Add refrigerant. | |
or continuously |
|
| |
Control contacts fused | Replace control. | ||
| |||
| Air in system | Purge system. | |
| Partially plugged or plugged expansion valve | Clean or replace as needed. | |
| or ®lter drier |
| |
| Defective insulation | Replace or repair as needed. | |
| Service load | Keep doors and windows closed. | |
| Inefficient compressor | Check valves, and replace if necessary. | |
Unusual or loud system | Piping vibration | Support piping as required. | |
noises |
|
| |
| Check for loose pipe connections. | ||
|
| ||
| Expansion valve hissing | Add refrigerant. | |
|
| Check for plugged liquid line ®lter drier. | |
| Compressor noisy | Check valve plates for valve noise. | |
|
| Replace compressor (worn bearings). | |
|
| Check for loose compressor holddown bolts. | |
|
|
|
38