Carrier installation instructions Electrical Data - 30MPA,MPW Units

Models: 30MPA

1 16
Download 16 pages 15.5 Kb
Page 15
Image 15
Table 3 — Electrical Data — 30MPA,MPW Units

EXAMPLE: Supply voltage is 240-3-60.

AB = 243 v

BC = 236 v

AC = 238 v

Average Voltage =

243 + 236 + 238

 

3

= 239 v

Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v

(BC) 239 – 236 = 3 v

(AC) 239 – 238 = 1 v

Maximum deviation is 4 v. Determine percent voltage imbalance:

% Voltage Imbalance =

100 x

4

 

239

 

=

1.7%

 

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local utility company immediately.

Table 3 — Electrical Data — 30MPA,MPW Units

UNIT SIZE

VOLTS

VOLTAGE*

 

COMPRESSOR

 

UNIT

 

 

30MPA,MPW

NAMEPLATE

Min

Max

Quantity

LRA

MCA

ICF

MOCP

Rec

(3 ph, 60 Hz)

(ea.)

Fuse

 

 

 

 

 

 

 

 

 

208/230

187

253

 

 

195

66.4

224.5

90

80

015

380

342

418

2

 

123

37.6

139.7

50

45

460

414

508

 

95

33.1

109.7

45

40

 

 

 

 

575

518

632

 

 

80

27.5

92.2

35

35

 

208/230

187

253

 

 

239

80.6

274.8

110

90

020

380

342

418

2

 

145

53.4

168.7

70

60

460

414

508

 

125

40.3

142.9

50

45

 

 

 

 

575

518

632

 

 

80

32.2

94.3

45

40

 

208/230

187

253

 

 

340

125.6

395.8

175

150

030

380

342

418

2

 

196

76.5

230.0

110

90

460

414

508

 

179

60.5

205.9

80

70

 

 

 

 

575

518

632

 

 

132

53.3

155.7

70

60

 

208/230

187

253

 

 

300

166.7

402.6

200

200

040

380

342

418

3

 

139

87.4

192.8

110

100

460

414

508

 

150

75.1

196.2

90

90

 

 

 

 

575

518

632

 

 

109

64.7

148.8

80

70

 

208/230

187

253

 

 

340

181.4

451.6

225

200

045

380

342

418

3

 

196

110.5

264.0

125

125

460

414

508

 

179

87.4

232.8

110

100

 

 

 

 

575

518

632

 

 

132

77.0

179.4

100

90

 

LEGEND

ICF

Maximum instantaneous current flow during starting.

kcmil

Thousand circular mils

LRA

Locked rotor amps.

MCA

Minimum circuit amps (for wire sizing). Complies with

 

NEC, Section 430-24.

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code (U.S.A.)

Rec

Recommended dual element fuse amps (150% of com-

Fuse

pressor RLA). Size up to the next standard fuse size.

*Supply Range — Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed range limits.

NOTES:

1.All units have one field power terminal block.

2.Maximum incoming wire size is as follows: For units with terminal block:

350 kcmil for unit sizes 030-045; 208/230-3-60 voltages. 2/0 for all other unit sizes; all voltages.

For units with optional non-fused disconnect:

350 kcmil for unit sizes:

030-045; 208/230-3-60 voltages. 045; 380-3-60 voltage.

3/0 for unit sizes:

015,020; 208/230-3-60 voltages.

020-040; 380-3-60 voltage.

030-045; 460-3-60 and 575-3-60 voltages.

2 AWG for unit sizes: 015; 380-3-60 voltage.

015-020; 460-3-60 and 575-3-60 voltages.

3.Additional control circuit power is not required.

4.Any field modification of factory wiring must be in compliance with all applicable codes. Field-installed power wires must be rated 75 C minimum.

5.Use copper conductors only.

6.Control circuit power supply is 24-v single phase. Control power is supplied by the factory-installed control transformer.

15

Page 15
Image 15
Carrier installation instructions Electrical Data - 30MPA,MPW Units