EXAMPLE: Supply voltage is
AB = 243 v
BC = 236 v
AC = 238 v
Average Voltage = | 243 + 236 + 238 |
| 3 |
= 239 v
Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance = | 100 x | 4 |
|
239 |
| ||
= | 1.7% |
|
|
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local utility company immediately.
Table 3 — Electrical Data — 30MPA,MPW Units
UNIT SIZE | VOLTS | VOLTAGE* |
| COMPRESSOR |
| UNIT |
|
| |||
30MPA,MPW | NAMEPLATE | Min | Max | Quantity | LRA | MCA | ICF | MOCP | Rec | ||
(3 ph, 60 Hz) | (ea.) | Fuse | |||||||||
|
|
|
|
|
|
|
| ||||
| 208/230 | 187 | 253 |
|
| 195 | 66.4 | 224.5 | 90 | 80 | |
015 | 380 | 342 | 418 | 2 |
| 123 | 37.6 | 139.7 | 50 | 45 | |
460 | 414 | 508 |
| 95 | 33.1 | 109.7 | 45 | 40 | |||
|
|
| |||||||||
| 575 | 518 | 632 |
|
| 80 | 27.5 | 92.2 | 35 | 35 | |
| 208/230 | 187 | 253 |
|
| 239 | 80.6 | 274.8 | 110 | 90 | |
020 | 380 | 342 | 418 | 2 |
| 145 | 53.4 | 168.7 | 70 | 60 | |
460 | 414 | 508 |
| 125 | 40.3 | 142.9 | 50 | 45 | |||
|
|
| |||||||||
| 575 | 518 | 632 |
|
| 80 | 32.2 | 94.3 | 45 | 40 | |
| 208/230 | 187 | 253 |
|
| 340 | 125.6 | 395.8 | 175 | 150 | |
030 | 380 | 342 | 418 | 2 |
| 196 | 76.5 | 230.0 | 110 | 90 | |
460 | 414 | 508 |
| 179 | 60.5 | 205.9 | 80 | 70 | |||
|
|
| |||||||||
| 575 | 518 | 632 |
|
| 132 | 53.3 | 155.7 | 70 | 60 | |
| 208/230 | 187 | 253 |
|
| 300 | 166.7 | 402.6 | 200 | 200 | |
040 | 380 | 342 | 418 | 3 |
| 139 | 87.4 | 192.8 | 110 | 100 | |
460 | 414 | 508 |
| 150 | 75.1 | 196.2 | 90 | 90 | |||
|
|
| |||||||||
| 575 | 518 | 632 |
|
| 109 | 64.7 | 148.8 | 80 | 70 | |
| 208/230 | 187 | 253 |
|
| 340 | 181.4 | 451.6 | 225 | 200 | |
045 | 380 | 342 | 418 | 3 |
| 196 | 110.5 | 264.0 | 125 | 125 | |
460 | 414 | 508 |
| 179 | 87.4 | 232.8 | 110 | 100 | |||
|
|
| |||||||||
| 575 | 518 | 632 |
|
| 132 | 77.0 | 179.4 | 100 | 90 |
| LEGEND |
ICF | — Maximum instantaneous current flow during starting. |
kcmil | — Thousand circular mils |
LRA | — Locked rotor amps. |
MCA | — Minimum circuit amps (for wire sizing). Complies with |
| NEC, Section |
MOCP | — Maximum Overcurrent Protection |
NEC | — National Electrical Code (U.S.A.) |
Rec | — Recommended dual element fuse amps (150% of com- |
Fuse | pressor RLA). Size up to the next standard fuse size. |
*Supply Range — Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed range limits.
NOTES:
1.All units have one field power terminal block.
2.Maximum incoming wire size is as follows: For units with terminal block:
350 kcmil for unit sizes
For units with optional
350 kcmil for unit sizes:
3/0 for unit sizes:
015,020;
2 AWG for unit sizes: 015;
3.Additional control circuit power is not required.
4.Any field modification of factory wiring must be in compliance with all applicable codes.
5.Use copper conductors only.
6.Control circuit power supply is
15