Carrier 38AQS008 specifications Dimensions

Models: 38AQS008

1 20
Download 20 pages 49.01 Kb
Page 4
Image 4
Fig. 2 — Dimensions

UNIT

UNIT

UNIT

 

WEIGHT CHART (WITH ALUMINUM COIL)

 

 

WEIGHT CHART (WITH COPPER COIL)

 

W/ALUMINUM COIL

W/COPPER COIL

Std Unit

Corner W

Corner X

Corner Y

Corner Z

Std Unit

Corner W

Corner X

Corner Y

Corner Z

38AQS008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dim. A

Dim. B

Dim. A

Dim. B

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

 

60 Hz

1-8

1-5

1-912

1-434

540

245

132

60

100

45

133

60

175

80

608

276

160

73

117

53

142

64

189

86

 

[508.0]

[431.8]

[546.0]

[425]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 Hz

1-6

1-7

1-712

1-634

594

270

114

52

114

52

183

83

183

83

662

299

142

64

131

59

192

87

197

89

 

[457.2]

[482.6]

[495.3]

[476.3]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1. Dimensions in [ ] are in millimeters.

2. Center of Gravity. See chart for dimensions.

3.Manual background Direction of airflow.

4.Minimum clearance (local codes or jurisdiction may prevail):

a.Bottom to combustible surfaces, 0 in. (0 mm)

b.Outdoor coil, for proper airflow, 36 in. (914 mm) one side, 12 in. (305 mm) the other. The side getting the greater clearance is optional.

c.Overhead, 60 in. (1524 mm) to assure proper outdoor-fan operation.

d.Between units, control box side, 42 in. (1067 mm) per National Electrical Code (NEC, U.S.A.).

e.Between unit and ungrounded surfaces, control box side, 36 in. (914 mm) per NEC (U.S.A.).

f.Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. (1067 mm) per NEC (U.S.A.).

5.With the exception of the clearance for the outdoor coil as stated in note 4b, a removable fence or barricade requires no clearance.

6.Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.

7.Vertical center of gravity is approximately 40% of total unit height.

 

ELECTRICAL CONNECTIONS

 

 

 

 

 

 

 

 

CONNECTION SIZES

 

AA

 

138Dia. [35] Field Power Supply Hole

BB

 

2Dia. [51] Power Supply Knock-Out

CC

 

212Dia. [64] Power Supply Knock-Out

DD

 

78Dia. [22] Field Control Wiring Hole

 

SERVICE VALVE CONNECTIONS

 

 

 

 

 

 

UNIT

 

SUCTION

 

LIQUID

38AQS008

 

118[28.6]

 

12[12.7]

Fig. 2 — Dimensions

4

Page 4
Image 4
Carrier 38AQS008 specifications Dimensions