Cooling Mode Operation — See Fig. 16.

5.Remove crankcase heater from compressor base.

6.Remove compressor holddown bolts and lift compres- sor off basepan.

7.Remove compressor from unit.

8.Clean system. Add new liquid line filter drier (biflow type).

9.Install new compressor and position in unit. Connect suc- tion and discharge lines to compressor. Connect high pres- sure switch. Ensure that compressor holddown bolts are in place. Connect wiring. Install crankcase heater.

10.Evacuate and recharge unit.

11.Restore unit power.

Cooling Mode Operation — See Fig. 16.

1.Hot refrigerant gas from compressor flows through the reversing valve and is directed to the outdoor coil vapor header.

2.Once at the outdoor coil vapor header, hot refrigerant gas flows up to check valve A,which is closed. All refrig- erant is then directed to complete a path through the lower 6 coil circuits (6 passes in each circuit).

3.Refrigerant flows through from the liquid header side out- lets into the transfer header, where it flows upward.

4.Refrigerant leaves the transfer header through side con- nections in 4 locations and enters the middle coil circuits (4 coil circuits above check valve A).

5.Refrigerant leaves the 4 middle coil circuit and enters the top portion of vapor header. The refrigerant moves up to the top 2 remaining coil circuits, where it enters the sub- cooler section.

Fig. 12 — Cleaning Outdoor Coil

Fig. 13 — Propping Up Top Panel

Fig. 14 — Separating Coil Sections

Fig. 15 — Outdoor-Fan Adjustment

6.Subcooled refrigerant leaves the coil circuits through the side outlets. It passes through check valve Binto the system liquid line and then into the indoor coil.

7.Liquid refrigerant is expanded and evaporated to a low- pressure vapor in the indoor coil. Refrigerant vapor then returns to the outdoor unit through the system vapor line, where it is drawn through the reversing valve and accu- mulator and back to the compressor suction connection.

Heating Mode Operation — See Fig. 17.

1.Hot gas from compressor flows through the reversing valve and is directed to the system vapor line and indoor coil vapor header (not shown). Refrigerant is condensed and subcooled in the indoor coil and returns to the outdoor unit through the system liquid line.

2.Check valve Bis closed and all liquid refrigerant enters the liquid header.

3.Refrigerant leaves the liquid header through 12 loca- tions. It is then expanded in fixed orifice metering de- vices contained within the outlet tubes.

4.Refrigerant evaporates to low pressure vapor as it com- pletes its passage through the 12 parallel coil circuits (6 passes each).

5.Refrigerant moves from the coil circuits into the vapor header, where it is drawn through the reversing valve and accumulator and back to compressor suction connection.