![Fig. 3 — Rigging Label](/images/new-backgrounds/33936/339369x1.webp)
| MAX WEIGHT |
|
|
|
|
|
|
|
|
| |||
UNIT | w/Al | w/Cu |
| A |
| B |
| C | |||||
38AQS008 | Coil | Coil |
|
|
|
|
|
|
|
|
| ||
| Lb | Kg | Lb | Kg | in. |
| mm | in. |
| mm | in. |
| mm |
60 Hz | 590 | 268 | 658 | 298 | 45.0 |
| 1143 | 38.5 |
| 989 | 43.5 |
| 1105 |
50 Hz | 644 | 292 | 712 | 323 |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 3 — Rigging Label
Fig. 4 — Compressor Mounting
All field wiring must comply with NEC (U.S.A.) and lo- cal requirements.
Install field wiring as follows:
1.Install conduit through side panel openings.
2.Install power lines to connections as shown in Fig. 8. Wrap connections with electrical tape.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 4). Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 4, Note 2, to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase im- balance constitutes abuse and may cause damage to elec- trical components. Such operation would invalidate any ap- plicable Carrier warranty.
ACCESSORY ELECTRIC HEAT — If the system is to be equipped with an accessory electric heater, refer to the 40RMQ008 installation instructions and Tables 5A and 5B.
FIELD CONTROL WIRING — Install a
Route thermostat cable or equivalent single leads of col- ored wire from subbase terminals to
1.Connect thermostat wires to screw terminals of low- voltage connection board.
2.Pass the control wires through the hole provided in the corner post. (See Fig. 10.)
3.Feed wire through the raceway built into the corner post to the
NOTE: 39 VA is available for
NOTE: For wire runs, use the following insulated wire:
LENGTH | INSULATION |
| SIZE | ||
Ft | M | RATING (C) | AWG |
| sq mm |
35 | 18 |
| 0.82 | ||
35 | 16 |
| 1.30 | ||
Over 75 | Over 22.9 | 35 | 14 |
| 2.08 |
LEGEND
AWG — American Wire Gage
All wire larger than no. 18 AWG (American Wire Gage) cannot be directly connected to the thermostat and will re- quire a junction box and splice at the thermostat.
5