Carrier 38AQS008 specifications A - Accessory Electric Heater Data 60 Hz

Models: 38AQS008

1 20
Download 20 pages 49.01 Kb
Page 8
Image 8
Table 5A — Accessory Electric Heater Data (60 Hz)

Table 5A — Accessory Electric Heater Data (60 Hz)

 

 

 

 

 

 

 

 

 

 

 

UNIT

HEATER

V-PH-Hz

NOMINAL kW

HEATER

MCA*

MOCP*

 

40RMQ

PART NO.

AMPS

 

 

 

 

 

 

 

CAELHEAT001A00

240-3-60

 

12.0

25.6

30

 

 

CAELHEAT002A00

480-3-60

5

6.0

12.3

15

 

 

CAELHEAT003A00

575-3-60

 

5.0

11.9

15

 

 

CAELHEAT004A00

240-3-60

 

24.1

40.7

50

 

 

CAELHEAT005A00

480-3-60

10

12.0

19.8

25

 

 

CAELHEAT006A00

575-3-60

 

10.0

18.1

25

 

 

CAELHEAT007A00

240-3-60

 

36.0

55.7

80

008

CAELHEAT008A00

480-3-60

15

18.0

27.4

40

 

 

CAELHEAT009A00

575-3-60

 

15.1

24.4

35

 

 

CAELHEAT010A00

240-3-60

 

60.1

85.8

125

 

 

CAELHEAT011A00

480-3-60

25

30.1

42.4

60

 

 

CAELHEAT012A00

575-3-60

 

25.1

67.0

50

 

 

CAELHEAT013A00

240-3-60

 

84.0

115.8

175

 

 

CAELHEAT014A00

480-3-60

35

42.1

57.4

80

 

 

CAELHEAT015A00

575-3-60

 

35.1

49.5

70

 

 

 

 

 

 

 

 

LEGEND

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (Amps)

*Sizes shown are for single-point connection of electric heat acces- sory and air handler.

NOTES:

1.MCA and MOCP values apply to both standard and alternate factory- supplied motors.

2.Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine heater capacity (kW) at unit nameplate voltage, multi- ply 240-v, 480-v, or 575-v capacity by multipliers found in table below.

 

HEATER RATING

 

 

 

ACTUAL HEATER VOLTAGE

 

 

 

 

VOLTAGE

200

208

230

240

400

440

460

480

550

575

600

 

240

.694

.751

.918

1

 

480

.694

.840

.918

1

575

.915

1

1.089

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The following equation converts kW of heat energy to Btuh:

 

 

 

 

kW x 3.412 = Btuh.

 

 

 

 

 

 

 

 

 

 

 

Table 5B — Accessory Electric Heater Data (50 Hz)

 

 

 

 

 

 

 

 

 

 

 

UNIT

HEATER

V-PH-Hz

NOMINAL kW

HEATER

MCA*

MOCP*

 

40RMQ

PART NO.

AMPS

 

 

 

 

 

 

 

CAELHEAT002A00

400-3-50

3.47

5.0

11.1

15

 

 

CAELHEAT001A00

230-3-50

4.59

11.5

25.0

30

 

 

CAELHEAT005A00

400-3-50

6.94

10.0

17.3

25

 

 

CAELHEAT004A00

230-3-50

9.18

23.1

39.5

50

 

 

CAELHEAT008A00

400-3-50

10.42

15.0

23.6

30

 

 

CAELHEAT007A00

230-3-50

13.78

34.6

53.9

80

 

 

CAELHEAT011A00

400-3-50

17.36

25.1

36.2

50

008

CAELHEAT010A00

230-3-50

22.96

57.6

82.6

110

CAELHEAT014A00

400-3-50

24.31

35.1

48.7

70

 

 

 

 

CAELHEAT013A00

230-3-50

32.14

80.7

111.5

175

 

 

CAELHEAT017A00

400-3-50

6.94

10.0

23.0

30

 

 

CAELHEAT016A00

230-3-50

9.18

23.1

39.5

50

 

 

CAELHEAT020A00

400-3-50

13.89

20.0

35.5

50

 

 

CAELHEAT019A00

230-3-50

18.37

46.1

79.9

110

 

 

CAELHEAT023A00

400-3-50

20.83

30.1

48.1

70

 

 

CAELHEAT022A00

230-3-50

27.55

69.2

108.7

150

 

 

 

 

 

 

 

 

LEGEND

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (Amps)

*Sizes shown are for single-point connection of electric heat acces- sory and air handler.

NOTES:

1.MCA and MOCP values apply to both standard and alternate factory- supplied motors.

2.Electrical resistance heaters are rated at 230 v or 400 v. To de- termine heater capacity (kW) at unit nameplate voltage, multiply 230-v or 400-v capacity by multipliers found in table below.

HEATER RATING

 

 

ACTUAL HEATER VOLTAGE

 

 

VOLTAGE

220

230

 

240

380

 

400

415

230

.915

1.0

 

1.084

 

400

 

0.903

 

1.0

1.076

 

 

 

 

 

 

 

 

 