A. Preliminary Information
OUTDOOR: MODEL NO. |
|
| SERIAL | NO. |
| ||||
INDOOR: AIR HANDLER MANUFACTURER |
|
|
|
|
|
| |||
MODEL NO. |
|
| SERIAL | NO. |
| ||||
ADDITIONAL ACCESSORIES |
|
|
|
|
|
|
B.
OUTDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
IS THERE ANY SHIPPING DAMAGE? |
|
|
|
| (Y/N) |
|
|
|
|
| |||||
IF SO, WHERE: |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
WILL THIS DAMAGE PREVENT UNIT |
| (Y/N) |
|
|
|
|
|
|
|
|
|
| |||
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? | (Y/N) |
|
|
| |||||||||||
HAS THE GROUND WIRE BEEN CONNECTED? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
| |||
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
| ||||||||||||
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
|
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
(Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CONTROLS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
ARE THERMOSTAT AND |
|
|
|
|
|
|
|
|
| ||||||||||
CONNECTIONS MADE AND CHECKED? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? | (Y/N) |
|
|
|
|
|
| ||||||||||||
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? | (Y/N) |
|
|
|
|
| |||||||||||||
INDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? | (Y/N) |
|
| ||||||||||||||||
ARE PROPER AIR FILTERS IN PLACE? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? | (Y/N) |
|
| ||||||||||||||||
DO THE FAN BELTS HAVE PROPER TENSION? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
| |||||||
HAS CORRECT FAN ROTATION BEEN CONFIRMED? |
| (Y/N) |
|
|
|
|
|
|
|
|
| ||||||||
PIPING |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED? | (Y/N) |
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR COIL, INDOOR COIL, TXV (Thermostatic Expansion Valve), SOLENOID VALVES, FILTER DRIER, REVERSING VALVE, CHECK VALVE, AND FUSIBLE PLUGS WITH A
LEAK DETECTOR? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
LOCATE, REPAIR, AND REPORT ANY LEAKS. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? | (Y/N) |
|
| |||||||||||||||||||
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? |
| (Y/N) |
|
| ||||||||||||||||||
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE INTO VIEW IN THE COMPRESSOR SIGHT GLASS? | ||||||||||||||||||||||
(Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CHECK VOLTAGE IMBALANCE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
AB |
|
|
| V | AC |
|
| V | BC | V |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
(AB + AC + BC)/3 = AVERAGE VOLTAGE = |
|
|
|
| V |
|
|
|
|
|
|
|
|
| ||||||||
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = |
|
|
| V |
|
|
|
|
|
| ||||||||||||
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = |
|
| % |
|
|
|
| |||||||||||||||
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! |
|
|
|
|
|
| ||||||||||||||||
CALL LOCAL POWER COMPANY FOR ASSISTANCE. |
|
|
|
|
|
|
|
|
|
|
|