6.1.12Remote Speed Adjustment Potentiometer Kit (Non-ECM Models)

The remote speed adjustment potentiometer kit provides controller-mounted engine speed adjustment. The adjustment range is approximately ±5%. Some applications locate this potentiometer with the switchgear. This kit requires an electronic governor on the generator set. See Figure 6-26. See Section 6.2, Accessory Connections, for terminal identifications.

1

 

1. Optional Remote Speed Pot

BR-273000-C

 

Figure 6-26 Remote Speed Adjustment Potentiometer Connection, Typical

6.1.13 Run Relay Kit

The run relay kit energizes only when the generator set runs. Use the run relay kit to control air intake and radiator louvers, alarms, and/or other signalling devices. See Figure 6-27 and Figure 6-28.

6.1.14 Shunt-Trip Line Circuit Breaker

A shunt-trip line circuit breaker provides a 12- or 24-DC volt solenoid within the line circuit breaker case that can energize the trip mechanism. This feature allows the circuit breaker to be tripped by a customer-selected fault such as alternator overload, overspeed, overvoltage, or defined common fault. Connection requires a shunt-trip wiring kit and a dry contact kit. See Figure 6-29.

273705

Figure 6-27 Run Relay Kit

TB10

GM16088A-A

Figure 6-28 Run Relay Connections

Typical Connection:

TB6--RDO1 Overspeed (39),

TB8--RDO18 Defined Common Fault (32A),

TB8--RDO20 Overvoltage (26), or

GM16088A-H

TB9--RDO30 Load Shed kW Overload

 

Figure 6-29 Shunt-Trip Line Circuit Breaker and Shunt-Trip Wiring Kit Connections

TP-6200 10/12

Section 6 Accessories 181

Page 181
Image 181