TP-6200 10/12 181Section6 Accessories
6.1.12 Remote Speed AdjustmentPotentiometer Kit (Non-ECMModels)
The remote speed adjustment potentiometer kit
provides controller-mounted engine speed adjustment.
The adjustment range is approximately ±5%. Some
applications locate this potentiometer with the
switchgear. This kit requires an electronic governor on
the generator set. See Figure 6-26. See Section 6.2,
Accessory Connections, for terminal identifications.
BR-273000-C
1
1. Optional Remote Speed Pot
Figure 6-26 Remote Speed Adjustment
Potentiometer Connection, Typical
6.1.13 Run Relay Kit
The run relay kit energizes only when the generator set
runs. Use the run relay kit to control air intake and
radiatorlouvers, alarms, and/or other signalling devices.
See Figure 6-27 and Figure 6-28.
6.1.14 Shunt-Trip Line Circuit Breaker
A shunt-trip line circuit breaker provides a 12- or 24-DC
volt solenoid within the line circuit breaker case that can
energize the trip mechanism. This feature allows the
circuitbreaker to be tripped by a customer-selected fault
such as alternator overload, overspeed, overvoltage, or
defined common fault. Connection requires a shunt-trip
wiring kit and a dry contact kit. See Figure 6-29.
273705
Figure 6-27 Run Relay Kit
GM16088A-A
TB10
Figure 6-28 Run Relay Connections
GM16088A-H
TypicalConnection:
TB6--RDO1Overspeed (39),
TB8--RDO18Defined Common Fault (32A),
TB8--RDO20Overvoltage (26), or
TB9--RDO30Load Shed kW Overload
Figure 6-29 Shunt-Trip Line Circuit Breaker and
Shunt-Trip Wiring Kit Connections