Kohler 20-3250 kW manual Controller Terminal Strip Identification

Models: 20-3250 kW

1 216
Download 216 pages 26.02 Kb
Page 187
Image 187

TB1 Terminal Strip—Engine Start and

TB4 Terminal Strip—Input Factory Connections

Emergency Stop Connections

 

 

Term. Description

Term. Description

1

DCH1 Battery charger fault

1

Emergency stop ground

2

DCH2 Low fuel

1A

Emergency stop

3

DCH3 Low coolant temp. with ECM models or

3

Remote start

 

warning default with non-ECM models

4

Remote start

 

4

DCH4 Field overvoltage with M4/M5/M7

 

 

 

 

 

alternators or warning default with

TB2 Terminal Strip—Analog Input Connections

 

non-M4/M5/M7 alternators

Term. Description

5

DCH5 Breaker Closed, Paralleling Applications

6

DCH6 Enable Synch, Paralleling Applications

1

ACH1 (CTS) Signal (non-ECM including Waukesha)

7

DCH7 Warning

2

ACH1 (CTS) Supply (non-ECM including Waukesha)

8

DCH8 Warning

3

ACH2 (OPS) Signal (non-ECM including Waukesha)

9

DCH9 Warning

4

ACH2 (OPS) Supply (non-ECM including Waukesha

10

DCH10 Warning

5

ACH3 Signal (air intake temp. for Waukesha)

11

DCH11 AFM Shutdown, Waukesha engine

6

ACH3 Supply (air intake temp. for Waukesha)

12

DCH12 Detonation Warning, Waukesha engine

7

ACH4 Signal (oil temp. for Waukesha)

13

DCH13 Detonation Shutdown,

8

ACH4 Supply (oil temp. for Waukesha)

 

Waukesha engine

9

ACH5 Signal

 

14

DCH14 Warning

10

ACH5 Supply

15

DCH15 Remote shutdown

11

ACH6 Signal

16

DCH16 Remote reset

12

ACH6 Supply (VSG for Volvo, GM, Doosan)

17

DCH17 VAR PF mode

13

ACH7 Signal (optional analog voltage adjust signal)

18

DCH18 Voltage lower

14

ACH7 Supply

19

DCH19 Voltage raise

15

N/C

20

DCH20 Air damper

16

ACH1 (CTS) Return (non-ECM)

21

DCH21 Idle mode functional with

17

ACH1 (CTS) Shield ground (non-ECM)

 

ECM-equipped engines only

18

ACH2 (OPS or OPS2) Return (non-ECM)

 

22

DCH1 Return

19

ACH2 (OPS) Shield ground (non-ECM)

23

DCH2 Return

20

ACH3 (IAT or OPS1) Return

24

DCH3 Return

21

ACH3 Shield ground

25

DCH4 Return

22

ACH4 (Oil Temp) Return

26

DCH5 Return

23

ACH4 Shield ground

27

DCH6 Return

24

ACH5 Return

28

DCH7 Return

25

ACH5 Shield ground

29

DCH8 Return

26

ACH6 Return

30

DCH9 Return

27

ACH6 Shield ground

31

DCH10 Return

28

ACH7 Return

32

DCH11 Return

29

ACH7 Shield ground

33

DCH12 Return

30

N/C

34

DCH13 Return

 

 

 

 

35

DCH14 Return

TB3 Terminal Strip—Accessory Power Output

36

DCH15 Return

Connections

37

DCH16 Return

Term. Description

38

DCH17 Return

39

DCH18 Return

1

+12 VDC (OEM use only)

40

DCH19 Return

2

+12 VDC (OEM use only)

41

DCH20 Return

3

+12 VDC (OEM use only)

42

DCH21 Return

4

Fused battery (+) (42A) (5 amp)

 

 

5Fused battery (+) (42A) (5 amp)

6Fused battery (+) (42A) (5 amp)

7

Battery (--)

Note: TB4-1 through TB4-21 are user definable with

factory defaults listed. Terminals TB4-3, TB4-4,

8

Battery (--)

9

Battery (--)

TB4-14, and TB4-21 have different functions

10

Battery (--)

depending upon the generator set configuration.

11

Battery (--)

See comments above.

12

Panel lamp output

See Menu 9—Input Setup for changing inputs.

Figure 6-38 Controller Terminal Strip Identification

TP-6200 10/12

Section 6 Accessories 187

Page 187
Image 187
Kohler 20-3250 kW manual Controller Terminal Strip Identification