Kohler 20-3250 kW manual Digital Aux. Input D05 Fixed

Models: 20-3250 kW

1 216
Download 216 pages 26.02 Kb
Page 197
Image 197

 

 

 

 

 

Relay

 

 

Inhibit

 

 

Status Event

Refer

 

 

Driver

 

Default

Time

Time

User-Defined

to

 

 

Output

 

Delay

Delay

or Fault

Menu

Digital Display

 

(RDO)

Range Setting

Selection

(sec.)

(sec.)

Settings

Digital Aux. Input

9, 10

D05

 

 

Fixed

0 sec.

 

 

Not adjustable

D05 Breaker

 

BREAKER

 

 

 

inhibit,

 

 

 

Closed w

 

CLOSED

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D06 ENABLE

 

 

 

20 sec.

 

 

Not adjustable

D06 w

 

SYNCH

 

 

 

inhibit,

 

 

 

 

 

 

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D09

 

 

Fixed

5 sec.

 

 

Not adjustable

D09 Low Fuel

 

LOW FUEL

 

 

 

inhibit,

 

 

 

Pressure Shutdown

 

SHUTDOWN

 

 

 

0 sec. delay

 

 

 

(125RZG only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D11

 

 

Fixed

0 sec.

 

 

Not adjustable

D11 Air/Fuel Module

 

AFM

 

 

 

inhibit,

 

 

 

(AFM) Shutdown ]

 

SHUTDOWN

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D12

 

 

Fixed

2 sec.

 

 

Not adjustable

D12 Detonation

 

DETON

 

 

 

inhibit,

 

 

 

Warning ]

 

WARNING

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D13

 

 

Fixed

0 sec.

 

 

Not adjustable

D13 Detonation

 

DETON

 

 

 

inhibit,

 

 

 

Sensing Module

 

SHUTDOWN

 

 

 

0 sec. delay

 

 

 

(DSM) Shutdown ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D13

 

 

Fixed

0 sec.

 

 

Not adjustable

D13 Knock Detection

 

KNOCK

 

 

 

inhibit,

 

 

 

Module (KDM)

 

SHUTDOWN

 

 

 

0 sec. delay

 

 

 

Shutdown ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input D14

9, 10

D14 LOW

 

RDO-19

Fixed

30 sec.

 

 

Not adjustable

Low Coolant Level,

 

COOLANT LVL

 

 

 

inhibit,

 

 

 

(with LCL switch) **

 

 

 

 

 

5 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D15 REMOTE

 

 

 

0 sec.

 

 

Not adjustable

D15 Remote

 

SHUTDOWN

 

 

 

inhibit,

 

 

 

Shutdown

 

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

 

 

 

 

 

 

 

Not adjustable

D16 Remote Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

 

 

 

 

 

 

 

Not adjustable

D17 VAR/PF mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

 

 

 

 

 

 

 

Not adjustable

D18 Voltage Lower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

 

 

 

 

 

 

 

Not adjustable

D19 Voltage Raise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D20

 

RDO-23 *

Fixed

0 sec.

 

 

Not adjustable

D20 Air Damper

 

AIR DAMPER

 

(lead 56)

 

inhibit,

 

 

 

Indicator (if used) **

 

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D21

 

RDO-21

Fixed inhibit time

0 sec.

 

0--600

Not adjustable

D21 Idle (speed)

 

IDLE MODE

 

 

 

inhibit,

 

or 9:99

 

Mode Function

 

ACTIVE

 

 

 

60 sec.

 

for

 

 

 

 

 

 

 

 

delay

 

infinity

 

 

 

 

 

 

 

 

 

 

 

ECM Red Alarm

10

ECM RED ALARM

 

 

 

 

 

 

Not adjustable

(was MDEC Yellow

 

 

 

 

 

 

 

 

 

Alarm) [[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECM Yellow Alarm

10

ECM YELLOW

 

 

 

 

 

 

Not adjustable

(was MDEC Yellow

 

ALARM

 

 

 

 

 

 

 

Alarm) [[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM Write

10

EEPROM WRITE

 

 

 

 

 

 

Not adjustable

Failure

 

FAILURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Stop

10

EMERGENCY

 

RDO-14

 

 

 

 

Not adjustable

Shutdown

 

STOP

 

(lead 48)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engine Cooldown

 

 

 

 

 

 

 

 

(see Time Delay--)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engine Derate Active

10

ENGINE DERATE

 

 

 

 

 

 

Not adjustable

 

 

 

ACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

 

** NFPA applications

 

 

 

[

Non-paralleling applications

 

 

 

[[ DDC/MTU engine with MDEC/ADEC

 

]

Waukesha-powered models

 

 

 

]] FAA only

 

 

 

 

w

Paralleling applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TP-6200 10/12

Appendix 197

Page 197
Image 197
Kohler 20-3250 kW manual Digital Aux. Input D05 Fixed