TP-6200 10/12 117Section 2 Operation
Local Programming Mode On
Menu 11—VoltageRegulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
REACTIVE DROOP
ENABLED N/Y Returns the user to reactive droop selection heading.
VARCONTROL
ENABLED N/Y Displays the VAR control selection (yes or no).
Press the Enter key.
Confirms the entry.
VARCONTROL
ENABLED YES
VARCONTROL ��
ENABLED YES
Entering YES enables the VARcontrol feature.
Note: A YES entry disables the PF control if previously activated.
VARCONTROL
ENABLED NO
OR
Confirms the entry.
Press the Enter key.
VARCONTROL
ENABLED NO
VARCONTROL
ENABLED NO
Entering NO disables the VARcontrol feature.
VARCONTROL
ENABLED YES
TOTAL K VAR #
KVARADJ ?.?
Displays total kVAR(running) and kVAR adjustment settings. Enter
the desired kVARadjustment using the numeric keys. Pressthe
Menu Right key prior to entering the decimal value.
Confirms the entry.
TOTAL K VAR #
KVARADJ #.#
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
TOTAL K VAR #
KVARADJ ?.?
GENERATING/ N/Y
ABSORBING
Displays the generating or absorbing kVARselection.
Note: The display sample may differ depending upon the previous
entries. The generating selection is the factory default setting.
Displays the generating kVARselection. Whenrequired, use the NO
key to choose absorbing kVAR.
Confirms the entry.
GENERATING YES
ABSORBING YES
Press the Enter key.
GENERATING NO
ABSORBING YES
OR
Confirms the entry.
ABSORBING NO
GENERATING YES
Displays the absorbing kVARselection. Whenrequired, use the NO
key to choose generating kVAR.
Press the Enter key.
VARCONTROL
ENABLED N/Y Returns the user to VAR control selection heading.