TP

 

 

 

 

Trouble Symptoms

 

 

 

 

 

 

 

-6200 10/12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Doesnot crank

 

Cranksbut doesnot start

Startshard

orNolow output voltage

Stopssuddenly

Lackspower

Overheats

Lowoil pressure

Highfuel consumption

Excessiveor abnormalnoise

Displayserror message/locksup

Exerciserun time and/orevent recordsinoperative

Probable Causes

Recommended Actions

Reference*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Publication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

x

 

 

 

 

 

 

 

 

 

 

Controller circuit board(s) inoperative

Replace the controller circuit board.

Gen. S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

Controller fault

Troubleshoot the controller.[

Gen. S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

x

 

 

x

 

 

 

 

 

 

 

Controller fuse blown

Replace the blown controller fuse. If the fuse blows again,

Section 2, W/D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

troubleshoot the controller.[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

TP-6200

10/12

Replace the controller master switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller master switch inoperative

 

x

 

 

 

 

 

 

 

 

 

 

 

 

Controller master switch in the

Move the controller master switch to the RUN or AUTO

Section 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF/RESET position

position.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

Engine start circuit open

Move the controller master switch to the RUN position to

Section 2, W/D,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

test the generator set. Troubleshoot the auto start circuit

Gen. I/M, S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and time delays.

ATS O/M, S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

x

 

 

 

 

 

 

 

Voltage regulation inoperative

Replace the controller fuse, If the fuse blows again,

Section Fuses,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

troubleshoot the controller.

Gen. S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

Controller firmware error

Review the controller display troubleshooting chart.

Section 4.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

Controller clock not set

Reset time and date.

Section 2.8.6,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Menu 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engine

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

x

 

 

x

 

 

x

 

 

 

Air cleaner clogged

Clean or replace the filter element.

Eng. O/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

x

 

 

 

x

 

x

x

 

 

Compression weak

Check the compression.[

Eng. S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

x

x

 

x

x

 

 

Engine overload

Reduce the electrical load. See the generator set spec

S/S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sheet for wattage specifications.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

Exhaust system leak

Inspect the exhaust system. Replace the inoperative

I/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exhaust system components.[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

Exhaust system not securely installed

Inspect the exhaust system. Tighten the loose exhaust

I/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system components.[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

x

 

x

 

 

x

 

 

 

Governor inoperative

Adjust the governor.[

Gen. S/M

Section4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

 

x

 

 

Valve clearance incorrect

Adjust the valves.[

Eng. S/M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x

 

 

Vibration excessive

Tighten all loose hardware.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Troubleshooting

 

 

x

x

 

 

x

 

 

 

 

 

 

Ignition system inoperative

Check the ignition system

Eng. O/M

 

 

 

 

 

 

 

 

 

 

 

 

 

(gas/gasoline only)

(spark plugs, spark plug wires, etc.).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual;

 

 

 

S/M—Service Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual

 

 

 

[ Have an authorized service distributor/dealer perform this service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

157

Page 157
Image 157
Kohler 20-3250 kW manual 6200 10/12 Doesnot crank