TP-6200 10/12174 Section 6 Accessories
6.1.11 Remote Serial Annunciator
RSA II is an annunciator panel offered in several kit
configurations to support Kohler power equipment. The
RSA is a remote serial annunciator Figure 6-18 and
Figure 6-19 that monitors the condition of the generator
set and/or ATSfrom a remote location. TheRSA alerts
the operator through visual and audible signals using
LED indication and a horn. An alarm silence and lamp
test switch are included.
The RSA meets NFPA110, Level 1 (2005) applications
thatrequire remote controls and alarms be powered by a
storage battery such as the engine starting battery. AC
adaptorkit GM62466-KP1 is available when NFPA is not
required.
The front panel decalsinclude areas that can be used to
identify user-selected fault inputs and identify
associated power system equipment.
An RSA annunciator can be used for a singlegenerator
set or with a combination of a generator set and
automatictransfer switch. In systems using more than a
single RSA, one must be designated as the master
device to broadcast to additional RSA annunciators,
designated as slave devices. Up to five RSA slave
devices can be used with an RSA master device. All
RSA annunciators factory default to the master device,
but can be changed with RSA II setup software that can
be connected to the RSA front panel via a universal
serial bus (USB) connection.
The RSA 1000 can be connected with the RSA II
provided that the master remote annunciator is an
RSA II.
RSA II setup software is required to make the RSA II
functional. Use your SecurID to access KOHLERnet,
clickon the TechToolsbutton, and follow the instructions
to download the files. See RSA II Setup Software at the
end of this document.
The RSA kits include components for surface mounting
or flush mounting.
Figure 6-20 shows the status of the system ready LED,
generator set running LED, communication statusLED,
common fault LED, common fault output, and horn for
each fault or status condition. See Figure 6-21 to
Figure 6-25 for RSA wiring connections.
If the RSA II is used with an Ethernet communication
network, order ModbusrEthernet converter
GM41143-KP2 and refer to TT-1405 Converters,
Connections, and Controller Setup for Network
Communication for system installation.
/Aux.
Figure 6-18 Remote Serial Annunciator (RSA II)
Figure 6-19 RSA II with ATS Controls
Modbusris
a
registered trademark o
f
Schneider Electric.