TP-6200 10/12118 Section 2 Operation Local Programming Mode On
Menu 11—VoltageRegulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
Displays the power factor control selection (yes or no).
PF CONTROL
ENABLED N/Y
Entering YES enables the power factor control feature.
Note: A YES entry disables the kVARcontrol if previously activated.
Confirms the entry.
PF CONTROL
ENABLED NO
PF CONTROL
ENABLED YES
Press the Enter key.
PF CONTROL
ENABLED YES
OR
Confirms the entry.
Press the Enter key.
PF CONTROL
ENABLED NO
PF CONTROL
ENABLED NO
AVERAGEPF #
PF ADJ ?.?
Displays the present running average power factor and power factor
adjustment settings. Enter the desired kVAR adjustment using the
numeric keys. Press the Menu Right key prior to entering the
decimal value.
Entering NO disables the power factor control feature.
PF CONTROL
ENABLED YES
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
Confirms the entry.
AVERAGEPF #
PF ADJ #.#
AVERAGEPF #
PF ADJ ?.?
LAGGING/ N/Y
LEADING
Displays the lagging or leading PF selection.
Note: The display sample may differ depending upon the previous
entries. The lagging selection is the factory default setting.
Displays the lagging PF selection. When required, use the NO key to
choose leading PF.
Confirms the entry.
LAGGING YES
LEADING YES
Press the Enter key.
LAGGING NO
OR
Confirms the entry.
LEADING YES
LEADING NO
LAGGING YES
Displays the leading PF selection. When required, use the NO key to
choose lagging PF.
Press the Enter key.
PF CONTROL
ENABLED N/Y Returns the user to the power factor control selection heading.