TP-6200 10/1296 Section 2 Operation LocalProgramming Mode On
2.8.8 Menu 8—Time Delays
Menu 8 displays the various time delays for cyclic
cranking and other engine-related starting and
shutdown features.
Theuser must enable the programming mode to edit the
display.
Cooldown Temperature Override. This feature
provides the ability to bypass (override) the generator
set’s smart cooldown temperature shutdown and force
thegenerator set to run for the full engine cooldown time
delay.
If the engine is above the preset temperature and the
unitis signalled to shut down, the unit will continue to run
for the duration of the TDEC.
If the engine is at or below the preset temperature and
theunit is signalled to shut down or the TDES is running,
the unit will shut down without waiting for the time delay
to expire.
Menu 8—Time Delays

Menu 8 Displays with Key Entries

Key
Entry Display Description
Input a menu number.
MENU 8
TIME DELAYS
Displays the starting aid time delay in minutes:seconds. When
required, use the numeric keys to set the new value. Press the Enter
key.
Displays the crank on time delay in minutes:seconds. When required,
use the numeric keys to set the new value. Press the Enter key.
Displays the crank pause time delay in minutes:seconds. When
required, use the numeric keys to set the new value. Press the Enter
key.
Displays the engine cooldown time delay in minutes:seconds. When
required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC
STARTINGAID ??:??
TIME DELAY MIN:SEC
CRANK ON ??:??
TIME DELAY MIN:SEC
CRANK PAUSE ??:??
TIME DELAY MIN:SEC
ENG COOLDOWN ??:??
TIME DELAY MIN:SEC
ENGINE START ??:??
Displays the engine start time delay in minutes:seconds. When
required, use the numeric keys to set the new value. Press the Enter
key.
Displays the corrected engine start time (minutes:seconds) delay
setting.
TIME DELAY MIN:SEC
ENGINE START ##:##
Displays the corrected starting aid time (minutes:seconds) delay
setting.
TIME DELAY MIN:SEC
STARTINGAID ##:##
Displays the corrected crank on time (minutes:seconds) delay setting.
TIME DELAY MIN:SEC
CRANK ON ##:##
Displays the corrected crank pause time (minutes:seconds) delay
setting.
TIME DELAY MIN:SEC
CRANK PAUSE ##:##
Displays the corrected engine cooldown time (minutes:seconds)
delay setting.
TIME DELAY MIN:SEC
ENG COOLDOWN ##:##
MAIN MENU NUMBER 8
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
COOLDOWN TEMPERATURE
OVERRIDE Y/N
Displays the cooldown temperature override. When required, use the
Yeskey to override the cooldown temperature time delay.