2.8.8Menu 8—Time Delays
Menu 8 displays the various time delays for cyclic cranking and other
The user must enable the programming mode to edit the display.
Cooldown Temperature Override. This feature provides the ability to bypass (override) the generator set’s smart cooldown temperature shutdown and force
the generator set to run for the full engine cooldown time delay.
If the engine is above the preset temperature and the unit is signalled to shut down, the unit will continue to run for the duration of the TDEC.
If the engine is at or below the preset temperature and the unit is signalled to shut down or the TDES is running, the unit will shut down without waiting for the time delay to expire.
Menu 8—Time Delays
Menu 8 Displays with Key Entries
Key |
|
|
Entry | Display | Description |
ENTER MENU NO.
MAIN MENU NUMBER 8
MENU 8
TIME DELAYS
TIME DELAY | MIN:SEC |
ENGINE START | ??:?? |
|
|
TIME DELAY | MIN:SEC |
ENGINE START | ##:## |
|
|
|
|
TIME DELAY | MIN:SEC |
STARTING AID | ??:?? |
|
|
Input a menu number.
Press the Enter key.
Displays the menu number and name.
Displays the engine start time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.
Displays the corrected engine start time (minutes:seconds) delay setting.
Displays the starting aid time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.
TIME DELAY | MIN:SEC |
STARTING AID | ##:## |
|
|
|
|
TIME DELAY | MIN:SEC |
CRANK ON | ??:?? |
|
|
TIME DELAY | MIN:SEC |
CRANK ON | ##:## |
|
|
TIME DELAY | MIN:SEC |
CRANK PAUSE | ??:?? |
|
|
TIME DELAY | MIN:SEC |
CRANK PAUSE | ##:## |
|
|
TIME DELAY | MIN:SEC |
ENG COOLDOWN | ??:?? |
|
|
TIME DELAY | MIN:SEC |
ENG COOLDOWN | ##:## |
COOLDOWN TEMPERATURE
OVERRIDEY/N
Displays the corrected starting aid time (minutes:seconds) delay setting.
Displays the crank on time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.
Displays the corrected crank on time (minutes:seconds) delay setting.
Displays the crank pause time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.
Displays the corrected crank pause time (minutes:seconds) delay setting.
Displays the engine cooldown time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.
Displays the corrected engine cooldown time (minutes:seconds) delay setting.
Displays the cooldown temperature override. When required, use the Yes key to override the cooldown temperature time delay.
96 Section 2 Operation | Local Programming Mode On |
|