2.8.8Menu 8—Time Delays

Menu 8 displays the various time delays for cyclic cranking and other engine-related starting and shutdown features.

The user must enable the programming mode to edit the display.

Cooldown Temperature Override. This feature provides the ability to bypass (override) the generator set’s smart cooldown temperature shutdown and force

the generator set to run for the full engine cooldown time delay.

If the engine is above the preset temperature and the unit is signalled to shut down, the unit will continue to run for the duration of the TDEC.

If the engine is at or below the preset temperature and the unit is signalled to shut down or the TDES is running, the unit will shut down without waiting for the time delay to expire.

Menu 8—Time Delays

Menu 8 Displays with Key Entries

Key

 

 

Entry

Display

Description

ENTER MENU NO. 1--15

MAIN MENU NUMBER 8

MENU 8

TIME DELAYS

TIME DELAY

MIN:SEC

ENGINE START

??:??

 

 

TIME DELAY

MIN:SEC

ENGINE START

##:##

 

 

 

 

TIME DELAY

MIN:SEC

STARTING AID

??:??

 

 

Input a menu number.

Press the Enter key.

Displays the menu number and name.

Displays the engine start time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.

Displays the corrected engine start time (minutes:seconds) delay setting.

Displays the starting aid time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.

TIME DELAY

MIN:SEC

STARTING AID

##:##

 

 

 

 

TIME DELAY

MIN:SEC

CRANK ON

??:??

 

 

TIME DELAY

MIN:SEC

CRANK ON

##:##

 

 

TIME DELAY

MIN:SEC

CRANK PAUSE

??:??

 

 

TIME DELAY

MIN:SEC

CRANK PAUSE

##:##

 

 

TIME DELAY

MIN:SEC

ENG COOLDOWN

??:??

 

 

TIME DELAY

MIN:SEC

ENG COOLDOWN

##:##

COOLDOWN TEMPERATURE

OVERRIDEY/N

Displays the corrected starting aid time (minutes:seconds) delay setting.

Displays the crank on time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.

Displays the corrected crank on time (minutes:seconds) delay setting.

Displays the crank pause time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.

Displays the corrected crank pause time (minutes:seconds) delay setting.

Displays the engine cooldown time delay in minutes:seconds. When required, use the numeric keys to set the new value. Press the Enter key.

Displays the corrected engine cooldown time (minutes:seconds) delay setting.

Displays the cooldown temperature override. When required, use the Yes key to override the cooldown temperature time delay.

96 Section 2 Operation

Local Programming Mode On

TP-6200 10/12

Page 96
Image 96
Kohler 20-3250 kW manual Menu 8-Time Delays, Menu 8 Displays with Key Entries