Relay

 

 

Inhibit

 

 

Status Event

Refer

 

Driver

 

Default

Time

Time

User-Defined

to

 

Output

 

Delay

Delay

or Fault

 

Menu

Digital Display

(RDO)

Range Setting

Selection

(sec.)

(sec.)

Settings

(Engine) J1939 CAN

10

J1939 CAN

 

 

 

 

 

Not adjustable

Engine Shutdown

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engine Stalled

10

ENGINE

 

 

 

 

 

Not adjustable

 

 

 

 

STALLED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Engine Start

 

 

 

 

 

 

 

(see Time Delay--)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EPS (Emergency

10

EPS

RDO-22

Fixed

1% of rated

 

 

Not adjustable

Power System)

 

SUPPLYING

 

 

line current

 

 

 

Supplying Load

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Overvoltage

 

 

 

 

 

 

 

Not adjustable

(see D04)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuel Level (see A04)

 

 

 

 

 

 

 

Fuel Valve Relay ]

10

FUEL VALVE

RDO-23 ]

 

 

 

 

Not adjustable

 

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Generator Set

10

 

RDO-15

 

 

 

 

Not adjustable

Running

 

 

 

(lead 70R)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground Fault

10

GROUND

 

 

 

 

 

Not adjustable

Detected

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Battery Voltage

10

HIGH

RDO-13

14.5--16.5 V (12 V)

16 V (12 V)

 

10

 

 

 

 

 

BATTERY

 

29--33 V (24 V)

32 V (24 V)

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Coolant

10

HI COOL

RDO-03

 

 

30

5

Not adjustable

Temperature

 

TEMP

(lead 36)

 

 

 

 

 

Shutdown

 

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Coolant

10

HI COOL

RDO-06

 

 

30

 

Not adjustable

Temperature Warning

 

TEMP

(lead 40)

 

 

 

 

 

 

 

 

 

WARNING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Oil Temperature

10

HI OIL TEMP

 

 

 

30

5

Not adjustable

Shutdown

 

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Oil Temperature

10

HI OIL TEMP

 

 

 

30

 

Not adjustable

Warning ]

[[

 

WARNING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Idle (speed) Mode

 

 

 

 

 

 

 

Function (see D21)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In Synch w

10

IN SYNCH

RDO-29 *

 

 

 

 

Not adjustable

 

 

 

 

 

 

 

 

 

 

Intake Air

 

10

INTAKE AIR

 

 

 

30

 

Not adjustable

Temperature

 

TEMP SDWN

 

 

 

 

 

 

Shutdown

[[

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake Air Temp.

10

INTAKE AIR

 

 

 

30

 

Not adjustable

Warning

[[

 

TEMP WARN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake Air Temp.

 

 

 

 

 

 

 

Warning (see A03) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake Air Temp.

 

 

 

 

 

 

 

Shutdown (see

 

 

 

 

 

 

 

 

A03)]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal Fault

10

INTERNAL

 

 

 

 

 

Not adjustable

Shutdown

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J1939 CAN

 

 

 

 

 

 

 

Shutdown (see

 

 

 

 

 

 

 

 

Engine J1939 CAN

 

 

 

 

 

 

 

 

Shutdown)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Knock Shutdown

 

 

 

 

 

 

 

(see D13) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW Overload

 

 

 

 

 

 

 

(see Load Shed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

** NFPA applications

 

 

 

[

Non-paralleling applications

 

 

[[ DDC/MTU engine with MDEC/ADEC

 

]

Waukesha-powered models

 

 

]] FAA only

 

 

 

 

w

Paralleling applications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

198 Appendix

TP-6200 10/12

Page 198
Image 198
Kohler 20-3250 kW manual Sec Settings Engine J1939 can Not adjustable Engine Shutdown