Analog Input Values. The analog input selection typically requires entering four values: low warning, high warning, low shutdown, and high shutdown. The analog values and time delays affect how and when the controller reacts. See Figure
Each analog input has the following nine features:
DOne warning enabled and one shutdown enabled
DOne inhibit time period
DOne warning delay and one shutdown delay
DTwo warning levels (high and low)
DTwo shutdown levels (high and low)
Note: The user must scale the analog input value in order to calculate the low/high warning and shutdown values based on a
| Time after Crank Disconnect | |||
|
|
|
| |
| Inhibit | Time | Time | |
Analog | Time | Delay | Delay | |
Values | Period ! | Period ! | Complete | |
|
|
|
| |
High shutdown value |
|
| High | |
is above the high |
|
| shutdown | |
warning value |
|
| function | |
|
|
|
| |
High warning value is |
| The | High warning | |
above the acceptable |
| function | ||
The | controller | |||
value | controller | does view |
| |
|
| |||
Acceptable analog | does not | the analog | System ready | |
view the | input signal | |||
value | status | |||
| analog | value and |
| |
|
| |||
Low warning value is | input signal | the time | Low warning | |
below the acceptable | value | delay | function | |
value |
| begins |
| |
|
|
|
| |
Low shutdown value |
|
| Low | |
is below the low |
|
| shutdown | |
warning value |
|
| function | |
|
|
|
|
Figure 2-19 Analog Input Logistics
Battle Switch/Fault Shutdown Override Switch. The battle switch function forces the system to ignore normal fault shutdowns such as low oil pressure and high engine temperature. The battle switch does not override the emergency stop and overspeed shutdown. When the battle switch function is enabled the generator set continues to run regardless of shutdown signals where potential engine/generator damage can occur.
When this input is enabled the yellow warning lamp illuminates and stored warning/shutdown events that are ignored continue to log in Menu 5—Event History.
Idle Mode Active. The idle time is defined by the digital
input time delay. Set the desired time in minutes:seconds,up to 10 minutes (600 seconds). If manual control of the idle mode is desired, an unlimited time can be entered as 9:99. The generator set will remain at idle speed as long as the input is active and the generator set master switch is in the AUTO position.
Shutdown Type A and Shutdown Type B. Choose shutdown type A for standard shutdowns where the red lamp illuminates and the alarm horn sounds. Choose shutdown type B for shutdowns where air damper indicator RDO-23 energizes for two seconds, the red lamp illuminates, and the alarm horn sounds.
| Local Programming Mode On | Section 2 Operation 99 |