Factory-Defined Settings

 

 

 

Relay

 

 

 

 

Inhibit

 

Status Event

Refer

 

Driver

Alarm

 

 

Default

Time

Time

to

 

Output

 

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Horn

Lamp

Range Setting

Selection

(sec.)

(sec.)

 

 

 

 

 

 

 

 

 

 

Access Code

14

 

 

 

 

User-Selectable

0 (zero)

 

 

(password)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Sensing Loss

10

AC SENSING

RDO-25 *

On

Warning

 

 

 

 

 

 

LOSS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Damper Control

10

 

 

 

 

 

 

 

 

(if used) **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Damper Indicator

 

 

 

 

 

 

 

 

 

(if used), see D20 **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air/Fuel Module

10

AFM ENG

 

 

 

Fixed

 

 

 

(AFM) Engine Start

 

START DELAY

 

 

 

 

 

 

 

Delay ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air/Fuel Module

10

AFM REMOTE

RDO-25 ]

Off

 

 

 

 

 

(AFM) Remote

 

START

 

 

 

 

 

 

 

Start ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air/Fuel Module

 

 

 

 

 

 

 

 

 

(AFM) Shutdown

 

 

 

 

 

 

 

 

 

(see D11) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alternator Protection

10

ALTERNATOR

 

On

Shutdown

 

 

 

 

Shutdown

 

PROTECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input 0

9

LOCAL BATT

 

 

 

Fixed

 

 

 

 

 

VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Inputs

9

USER-DEFINED

 

On

Shutdown

Default Values with

30 sec.

0--60

0--60

A01--A07

 

A01--A07

 

 

or

Warning Enabled:

inhibit,

 

 

 

 

 

 

 

Warning

HI warning 90%

5 sec. delay

 

 

 

 

 

 

 

 

LO warning 10%

 

 

 

 

 

 

 

 

 

HI shutdown 100%

 

 

 

 

 

 

 

 

 

LO shutdown 1%

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A01

 

On

Shutdown

Default Values with

30 sec.

 

 

A01 (non-ECM only)

 

COOLANT

 

 

or

Warning Enabled:

inhibit,

 

 

 

 

TEMP

 

 

Warning

HI/LO warning and

0 sec. delay

 

 

 

 

 

 

 

 

HI/LO shutdown are

warning,

 

 

 

 

 

 

 

 

all engine dependent

5 sec. delay

 

 

 

 

 

 

 

 

 

shutdown

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A02

 

On

Shutdown

Default Values with

30 sec.

 

 

A02 (non-ECM only)

 

OIL

 

 

or

Warning Enabled:

inhibit,

 

 

 

 

PRESSURE

 

 

Warning

HI/LO warning and

0 sec. delay

 

 

 

 

 

 

 

 

HI/LO shutdown are

warning,

 

 

 

 

 

 

 

 

all engine dependent

5 sec. delay

 

 

 

 

 

 

 

 

(255 psi max.)

shutdown

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A03

 

 

Shutdown

Default Values with

30 sec.

 

 

A03 ]

 

INTAKE AIR

 

 

or

Warning Enabled:

inhibit,

 

 

 

 

TEMP

 

 

Warning

HI/LO warning and

0 sec. delay

 

 

 

 

 

 

 

 

HI/LO shutdown are

warning

 

 

 

 

 

 

 

 

all engine dependent

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A04

 

 

 

Default Values with

30 sec.

 

 

A04 *

 

FUEL LEVEL

 

 

 

Warning Enabled:

inhibit,

 

 

 

 

 

 

 

 

HI/LO warning are

0 sec. delay

 

 

 

 

 

 

 

 

engine dependent

warning

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A04

 

On

Warning

Default Values with

30 sec.

 

 

A04 ]

 

OIL TEMP

 

 

 

Warning Enabled:

inhibit,

 

 

 

 

 

 

 

 

HI/LO warning are

0 sec. delay

 

 

 

 

 

 

 

 

engine dependent

warning

 

 

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9, 12

A06 ANALOG

 

Off

 

 

Volvo:

 

 

A06 VSG (Volvo,

 

AUXILIARY IN

 

 

 

 

0.5V=1250

 

 

GM, Doosan only)

 

 

 

 

 

 

4.5V=8750

 

 

 

 

 

 

 

 

 

GM/Doosan

 

 

 

 

 

 

 

 

 

60 Hz:

 

 

 

 

 

 

 

 

 

0.5V=2375

 

 

 

 

 

 

 

 

 

4.5V=2625

 

 

 

 

 

 

 

 

 

50 Hz:

 

 

 

 

 

 

 

 

 

0.5V=2327

 

 

 

 

 

 

 

 

 

4.5V=2624

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

**

NFPA applications

[

Non-paralleling applications

[[

DDC/MTU engine with MDEC/ADEC

]

Waukesha-powered models

]]

FAA only

w

Paralleling applications

 

 

24 Section 1 Specifications and Features

TP-6200 10/12

Page 24
Image 24
Kohler 20-3250 kW manual Factory-Defined Settings