2.8.14 Menu 14—Programming Mode
Menu 14 allows altering controller data either locally using the keypad or remotely using a PC or other device.
The user must enter a password (access code) to enable the programming mode.
Local Programming. Local programming is data alteration using the controller keypad and display.
Remote Programming. Remote programming is data alteration using devices connected to a communication port using KBUS or Modbusr including Monitor III software.
Note: Log into the local programming mode to edit the programming access code. The factory default access code is the number 0.
Use Menu 14 to change the access code. Record the new number and give the access code to authorized individuals only. Should the controller logic not accept the access code or if the new code number is lost, contact your local authorized distributor/dealer for password information.
The user chooses one of three programming modes:
D
D
D
Enter Yes to one mode to change the other two choices to No.
Note: Use the generator set controller to initially set up remote programming. Remote programming is not allowed from a PC unless the controller is first set for remote programming using Menu 14.
Note: After completing the programming always place the controller back in the Programming Mode Off position to prevent inadvertent program changes.
Modbusr is a registered trademark of Schneider Electric.
| Local Programming Mode On | Section 2 Operation 129 |