Menu 12—Calibration, continued

Menu 12 Displays with Key Entries (Scale AC Analog Inputs)

Key

 

 

Entry

Display

Description

GEN L3-L1 V

#

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L3-L1 V

#

 

 

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L3-L1 V

#

 

 

 

 

 

CALIB REF

#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE REGULATOR?

 

 

 

 

 

 

Y/N

CALIBRATE REGULATOR? YES

CALIBRATE REGULATOR?

Y/N

GEN VOLTAGE LL

GEN AMPS

GEN L1 AMPS

#

CALIB REF

?.?

AND

 

 

GEN L1 AMPS

#

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L1 AMPS

#

 

 

 

CALIB REF

#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L2 AMPS

#

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

 

 

 

 

GEN L2 AMPS

#

 

 

 

CALIB REF

?.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN L2 AMPS

#

 

 

 

CALIB REF

#

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-Phase Models only. Measure the generator set output voltage for three-phase models between L3-L1 using a voltmeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

Displays the calibrate regulator selection.

Note: After changing the meter calibration the voltage regulator should be calibrated—enter YES.

When required, use the YES key to calibrate the voltage regulator.

Confirms the entry.

Returns the user to the generator set line-to-line voltage heading.

Displays the generator set amps heading.

Note: The generator set must be running for the following steps.

Measure the generator set output current for single- and three-phase models at L1 using an AC ammeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

Measure the generator set output current for three-phase models at L2 using an AC ammeter and enter the result using the numeric keys. Press the Menu Right key prior to entering the decimal value.

Use the numeric keys to enter the decimal value. Press the Enter key.

Confirms the entry.

122 Section 2 Operation

Local Programming Mode On

TP-6200 10/12

Page 122
Image 122