TP-6200 10/12 25Section 1 Specifications and Features
Factory-Defined Settings
Status Event
or Fault
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range SettingLamp
Alarm
Horn
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Analog Aux. Input
A07
9A07
ANALOG VOLT
ADJUST
±10% of system
voltage over the range
of 0.5--4.5VDC
Battery Charger Fault
(see D01) **
Battle Switch
(Fault Shutdown
Override Switch)
9 BATTLE
SWITCH
Off Warning Fixed
Block Heater
Control[[
10 BLOCK HEATER
CONTROL
RDO only
Breaker Trip w10 BREAKER
TRIP
RDO-30 Off Warning
Common Protective
Relay Output w
10 COMMON PR
OUTPUT
RDO-31 wOff Warning
Critical Overvoltage
Shutdown
10 CRITICAL
OVERVOLTAGE
On Shutdown Fixed 275 volts
(L1--L2)
Cyclic Cranking 8 Off 1--6 crank cycles
10--30sec. crank on
1--60sec. pause
3
15 sec.
15 sec.
Defined Common
Faults
(each input value is
set separately)
10 DEFINED
COMMON
FAULT
RDO-18
(lead 32A)
On Shutdown
or
Warning
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Detonation Shutdown
(see D13) ]
Detonation Warning
(see D12) ]
Digital Aux. Input
D01--D21
9, 10 USER-DEFINED
D01--D21
On Shutdown
or
Warning
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Input
D01 Battery Charger
Fault **
9, 10 D01 BATTERY
CHARGER
FAULT
RDO-11
(lead 61)
On Warning Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D02 Low Fuel
Warning **
9, 10 D02
LOW FUEL
WARNING
RDO-08
(lead 63)
On Warning Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D03 Low Coolant
Temperature**
9, 10 D03 LOW
COOLANT
TEMP
RDO-05
(lead 35)
On Warning Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D04 Field
Overvoltage (M4,
M5, M7, or M10 alt.
only)
9, 10 D04
FIELD
OVERVOLTAGE
On Shutdown Fixed 1 sec.
inhibit,
15 sec.
delay
Digital Aux. Input
D05 Breaker
Closed w
9, 10 D05
BREAKER
CLOSED
Off Warning Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D06 w
9, 10 D06 ENABLE
SYNCH
20 sec.
inhibit, 0
sec. delay
Digital Aux. Input
D09 Low Fuel
Pressure Shutdown
(125RZG only)
9, 10 D09
LOW FUEL
SHUTDOWN
On Shutdown Fixed 5 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D11Air/Fuel Module
(AFM) Shutdown ]
9, 10 D11
AFM
SHUTDOWN
On Shutdown Fixed 0 sec.
inhibit,
0 sec. delay
* All models, except Waukesha-powered models. ** NFPAapplications
[Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
]Waukesha-powered models ]] FAA only
wParalleling applications