Factory-Defined Settings

 

 

 

Relay

 

 

 

 

Inhibit

 

Status Event

Refer

 

Driver

Alarm

 

 

Default

Time

Time

to

 

Output

 

 

Delay

Delay

or Fault

Menu

Digital Display

(RDO)

Horn

Lamp

Range Setting

Selection

(sec.)

(sec.)

 

 

 

 

 

 

 

 

 

 

Analog Aux. Input

9

A07

 

 

 

±10% of system

 

 

 

A07

 

ANALOG VOLT

 

 

 

voltage over the range

 

 

 

 

 

ADJUST

 

 

 

of 0.5--4.5 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Charger Fault

 

 

 

 

 

 

 

 

 

(see D01) **

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battle Switch

9

BATTLE

 

Off

Warning

Fixed

 

 

 

(Fault Shutdown

 

SWITCH

 

 

 

 

 

 

 

Override Switch)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Block Heater

10

BLOCK HEATER

RDO only

 

 

 

 

 

 

Control [[

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Breaker Trip w

10

BREAKER

RDO-30

Off

Warning

 

 

 

 

 

 

TRIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common Protective

10

COMMON PR

RDO-31 w

Off

Warning

 

 

 

 

Relay Output w

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Critical Overvoltage

10

CRITICAL

 

On

Shutdown

Fixed

275 volts

 

 

Shutdown

 

OVERVOLTAGE

 

 

 

 

(L1--L2)

 

 

 

 

 

 

 

 

 

 

 

 

Cyclic Cranking

8

 

 

Off

 

1--6 crank cycles

3

 

 

 

 

 

 

 

 

10--30 sec. crank on

15 sec.

 

 

 

 

 

 

 

 

1--60 sec. pause

15 sec.

 

 

 

 

 

 

 

 

 

 

 

 

Defined Common

10

DEFINED

RDO-18

On

Shutdown

Default shutdowns

30 sec.

0--60

0--60

Faults

 

COMMON

(lead 32A)

 

or

include:

inhibit,

 

 

(each input value is

 

FAULT

 

 

Warning

Emergency stop

5 sec. delay

 

 

set separately)

 

 

 

 

 

High coolant temp

 

 

 

 

 

 

 

 

 

Low oil pressure

 

 

 

 

 

 

 

 

 

Overcrank

 

 

 

 

 

 

 

 

 

Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

 

Detonation Shutdown

 

 

 

 

 

 

 

 

 

(see D13) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detonation Warning

 

 

 

 

 

 

 

 

 

(see D12) ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

USER-DEFINED

 

On

Shutdown

 

30 sec.

0--60

0--60

D01--D21

 

D01--D21

 

 

or

 

inhibit,

 

 

 

 

 

 

 

Warning

 

5 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D01 BATTERY

RDO-11

On

Warning

Fixed

0 sec.

 

 

D01 Battery Charger

 

CHARGER

(lead 61)

 

 

 

inhibit,

 

 

Fault **

 

FAULT

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D02

RDO-08

On

Warning

Fixed

0 sec.

 

 

D02 Low Fuel

 

LOW FUEL

(lead 63)

 

 

 

inhibit,

 

 

Warning **

 

WARNING

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D03 LOW

RDO-05

On

Warning

Fixed

0 sec.

 

 

D03 Low Coolant

 

COOLANT

(lead 35)

 

 

 

inhibit,

 

 

Temperature **

 

TEMP

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D04

 

On

Shutdown

Fixed

1 sec.

 

 

D04 Field

 

FIELD

 

 

 

 

inhibit,

 

 

Overvoltage (M4,

 

OVERVOLTAGE

 

 

 

 

15 sec.

 

 

M5, M7, or M10 alt.

 

 

 

 

 

 

delay

 

 

only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D05

 

Off

Warning

Fixed

0 sec.

 

 

D05 Breaker

 

BREAKER

 

 

 

 

inhibit,

 

 

Closed w

 

CLOSED

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D06 ENABLE

 

 

 

 

20 sec.

 

 

D06 w

 

SYNCH

 

 

 

 

inhibit, 0

 

 

 

 

 

 

 

 

 

sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D09

 

On

Shutdown

Fixed

5 sec.

 

 

D09 Low Fuel

 

LOW FUEL

 

 

 

 

inhibit,

 

 

Pressure Shutdown

 

SHUTDOWN

 

 

 

 

0 sec. delay

 

 

(125RZG only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Aux. Input

9, 10

D11

 

On

Shutdown

Fixed

0 sec.

 

 

D11 Air/Fuel Module

 

AFM

 

 

 

 

inhibit,

 

 

(AFM) Shutdown ]

 

SHUTDOWN

 

 

 

 

0 sec. delay

 

 

 

 

 

 

 

 

 

 

 

 

*

All models, except Waukesha-powered models.

**

NFPA applications

[

Non-paralleling applications

[[

DDC/MTU engine with MDEC/ADEC

]

Waukesha-powered models

]]

FAA only

w

Paralleling applications

 

 

TP-6200 10/12

Section 1 Specifications and Features 25