Factory-Defined Settings
|
|
| Relay |
|
|
|
| Inhibit |
|
Status Event | Refer |
| Driver | Alarm |
|
| Default | Time | Time |
to |
| Output |
|
| Delay | Delay | |||
or Fault | Menu | Digital Display | (RDO) | Horn | Lamp | Range Setting | Selection | (sec.) | (sec.) |
|
|
|
|
|
|
|
|
|
|
Analog Aux. Input | 9 | A07 |
|
|
| ±10% of system |
|
|
|
A07 |
| ANALOG VOLT |
|
|
| voltage over the range |
|
|
|
|
| ADJUST |
|
|
| of |
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery Charger Fault |
|
|
|
|
|
|
|
|
|
(see D01) ** |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battle Switch | 9 | BATTLE |
| Off | Warning | Fixed |
|
|
|
(Fault Shutdown |
| SWITCH |
|
|
|
|
|
|
|
Override Switch) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Block Heater | 10 | BLOCK HEATER | RDO only |
|
|
|
|
|
|
Control [[ |
| CONTROL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Breaker Trip w | 10 | BREAKER | Off | Warning |
|
|
|
| |
|
| TRIP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Common Protective | 10 | COMMON PR | Off | Warning |
|
|
|
| |
Relay Output w |
| OUTPUT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Critical Overvoltage | 10 | CRITICAL |
| On | Shutdown | Fixed | 275 volts |
|
|
Shutdown |
| OVERVOLTAGE |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Cyclic Cranking | 8 |
|
| Off |
| 3 |
|
| |
|
|
|
|
|
| 15 sec. |
|
| |
|
|
|
|
|
| 15 sec. |
|
| |
|
|
|
|
|
|
|
|
|
|
Defined Common | 10 | DEFINED | On | Shutdown | Default shutdowns | 30 sec. | |||
Faults |
| COMMON | (lead 32A) |
| or | include: | inhibit, |
|
|
(each input value is |
| FAULT |
|
| Warning | Emergency stop | 5 sec. delay |
|
|
set separately) |
|
|
|
|
| High coolant temp |
|
|
|
|
|
|
|
|
| Low oil pressure |
|
|
|
|
|
|
|
|
| Overcrank |
|
|
|
|
|
|
|
|
| Overspeed |
|
|
|
|
|
|
|
|
|
|
|
|
|
Detonation Shutdown |
|
|
|
|
|
|
|
|
|
(see D13) ] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Detonation Warning |
|
|
|
|
|
|
|
|
|
(see D12) ] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 |
|
| On | Shutdown |
| 30 sec. | ||
|
|
| or |
| inhibit, |
|
| ||
|
|
|
|
| Warning |
| 5 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D01 BATTERY | On | Warning | Fixed | 0 sec. |
|
| |
D01 Battery Charger |
| CHARGER | (lead 61) |
|
|
| inhibit, |
|
|
Fault ** |
| FAULT |
|
|
|
| 0 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D02 | On | Warning | Fixed | 0 sec. |
|
| |
D02 Low Fuel |
| LOW FUEL | (lead 63) |
|
|
| inhibit, |
|
|
Warning ** |
| WARNING |
|
|
|
| 0 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D03 LOW | On | Warning | Fixed | 0 sec. |
|
| |
D03 Low Coolant |
| COOLANT | (lead 35) |
|
|
| inhibit, |
|
|
Temperature ** |
| TEMP |
|
|
|
| 0 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D04 |
| On | Shutdown | Fixed | 1 sec. |
|
|
D04 Field |
| FIELD |
|
|
|
| inhibit, |
|
|
Overvoltage (M4, |
| OVERVOLTAGE |
|
|
|
| 15 sec. |
|
|
M5, M7, or M10 alt. |
|
|
|
|
|
| delay |
|
|
only) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D05 |
| Off | Warning | Fixed | 0 sec. |
|
|
D05 Breaker |
| BREAKER |
|
|
|
| inhibit, |
|
|
Closed w |
| CLOSED |
|
|
|
| 0 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D06 ENABLE |
|
|
|
| 20 sec. |
|
|
D06 w |
| SYNCH |
|
|
|
| inhibit, 0 |
|
|
|
|
|
|
|
|
| sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D09 |
| On | Shutdown | Fixed | 5 sec. |
|
|
D09 Low Fuel |
| LOW FUEL |
|
|
|
| inhibit, |
|
|
Pressure Shutdown |
| SHUTDOWN |
|
|
|
| 0 sec. delay |
|
|
(125RZG only) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Aux. Input | 9, 10 | D11 |
| On | Shutdown | Fixed | 0 sec. |
|
|
D11 Air/Fuel Module |
| AFM |
|
|
|
| inhibit, |
|
|
(AFM) Shutdown ] |
| SHUTDOWN |
|
|
|
| 0 sec. delay |
|
|
|
|
|
|
|
|
|
|
|
|
* | All models, except | ** | NFPA applications |
[ | [[ | DDC/MTU engine with MDEC/ADEC | |
] | ]] | FAA only | |
w | Paralleling applications |
|
|
| Section 1 Specifications and Features 25 |