6.1.7Low Fuel (Level/Pressure) Switch
Some
Note: The main tank or the transfer/day tank includes the low fuel level switch. The fuel tank supplier typically provides the low fuel level switch.
Figure |
Switch Rating |
| 12 volts DC minimum, 0.5 amp minimum |
|
|
|
| Wiring Recommendation | |
|
|
|
Gauge |
| mm (ft.) |
|
|
|
| 30.5 (100) | |
|
|
|
14 |
| 153 (500) |
|
|
|
10 |
| 305 (1000) |
Figure 6-11 Switch Rating & Wiring Recommendation
6.1.8Prime Power Switch Kit
The prime power switch kit prevents battery drain during generator set nonoperation periods and when the generator set battery cannot be maintained by an AC battery charger. See Figure
| 1 |
PRIME POWER | 2 |
SWITCH | |
|
|
GM20652-
1. Prime power decal (293668) | 2. Toggle switch (354464) |
Figure 6-12 Prime Power Switch Installation Location
Toggle switch shown in the prime power mode off position (contacts open)
Figure 6-13 Prime Power Switch Connections
Stop the generator set using the stopping procedures in Section 2.3.2, Stopping, before placing the generator set in the prime power mode. Move the prime power switch located on the back of the controller to the DOWN position. The controller including the digital display, LEDs, and alarm horn does not function when the generator set is in the prime power mode.
Move the prime power switch located on the back of the controller to the UP position and reset the controller time and date before attempting to start the generator set.
172 Section 6 Accessories |
|