GM13984-

Figure 6-39 Terminal Strips TB6, TB7, TB8, and TB9 on the Controller Connection Kit in the Junction Box

TB6 Terminal Strip—RDOs 1-7

TB9 Terminal Strip—RDOs 24-31

Term.

Description

Term.

Description

42A

Battery (+)

RDO24

Speed sensor fault

GND

Battery (--)

RDO25

Loss of AC sensing

N/C

 

RDO26

ECM loss of communication

RDO1

Overspeed (lead 39)

RDO27

Undervoltage

RDO2

Overcrank (lead 12)

RDO28

Overfrequency

RDO3

High coolant temperature shutdown (lead 36)

RDO29

Underfrequency

RDO4

Low oil pressure shutdown (lead 38)

RDO30

Load shed kW overload

RDO5

Low coolant temperature (lead 35)

RDO31

Load shed underfrequency

RDO6

High coolant temperature warning (lead 40)

3

Remote start

RDO7

Low oil pressure warning (lead 41)

4

Remote start

TB7 Terminal Strip—RDOs 8-17

Term.

Description

RDO8

Low fuel (lead 63)

RDO9

Master switch not in auto ( lead 80)

RDO10

NFPA 110 common alarm (lead 32)*

RDO11

Battery charger fault (lead 61)

RDO12

Low battery voltage (lead 62)

RDO13

High battery voltage

RDO14

Emergency stop (lead 48)

RDO15

Generator set running (lead 70R)

RDO16

Time delay engine cooldown (TDEC) (lead 70C)

RDO17

System ready (lead 60)

TB8 Terminal Strip—RDOs 18-23

Term.

Description

42A

Battery (+)

42A

Battery (+)

GND

Battery (--)

GND

Battery (--)

RDO18

Defined common fault (lead 32A)

RDO19

Low coolant level

RDO20

Overvoltage (lead 26)

RDO21

Idle mode

RDO22

EPS supplying load

RDO23

Air damper indicator (lead 56)

Note:Lead numbers shown in parentheses are the factory default wire designations.

Note:RDO-1 though RDO-31 are user definable with the

following factory defaults: emergency stop, high coolant temperature, low oil pressure, overcrank, and overspeed

*NFPA-110 common alarm faults include:

Air damper indicator (RDO--23) Battery charger fault (RDO--11) EPS supplying load (RDO--22) High battery voltage (RDO--13)

High coolant temperature warning (RDO--06) High coolant temperature shutdown (RDO--03) Low battery voltage (RDO--012)

Low coolant level (RDO--19)

Low coolant temperature warning (RDO--05) Low fuel (level or pressure) (RDO--08)

Low oil pressure warning (RDO--07) Low oil pressure shutdown (RDO--04) Master switch not in auto (RDO--09) Overcrank (RDO--02)

Overspeed (RDO--01)

Figure 6-40 Controller (Customer) Connection Kit Terminal Strip Identification with Relay Driver Outputs (RDOs)

188 Section 6 Accessories

TP-6200 10/12

Page 188
Image 188
Kohler 20-3250 kW RDO24, Gnd, RDO25, RDO26, RDO1, RDO27, RDO28, RDO29, RDO4, RDO30, RDO5, RDO31, RDO6, RDO7, RDO8